Submersible pump cables
PVC 3 Core Flat Cables PVC 4 Core Flat Cables PVC 3 Core Round Cables more

Submersible pump cables

Rubber 4 Core Flat Cables

Applications:

For continuous use in deep well to supply power to submersible pumps down to depths of 500 mtrs.

FEATURES:

Meets the requirement of CENELEC HD 22.1.S2, DIN VDE 0282 PART 810, IEC 245, CEI 20-19 & BS 6007, BS

6899. Cur, tear & abrasion resistant.

Exceptional long term performance.

Excellent resistant to oils, chemicals, ozone & solvents.

Excellent Impact Resistant.

Excellent Weather Resistant.

Performs & Looks like Vulcanize Rubber.

Construction :

CONDUCTOR RUBBER INSULATION RUBBER SHEATH Conductor Resistance at 20°C (max) ohms/km CURRENT
Rating at 40°C
Amps.
Nominal
Area in
Nos. & Dia.
of wire
Nominal
Thickness
Nominal
Core Dia.
Nominal
Thickness
Approx. Overall
Dimensions
Sq. mm. Nos. / mm mm mm mm Thickness
mm
Width
mm
1.50 22/0.30 0.80 3.25 1.30 6.00 15.80 12.10 14
2.50 36/0.30 0.90 3.84 1.30 6.50 18.00 7.41 18
4.00 56/0.30 1.00 4.50 1.45 7.60 21.00 4.95 26
6.00 85/0.30 1.00 5.30 1.50 7.90 24.30 3.30 31
10.00 140/0.30 1.00 6.50 1.80 9.90 29.70 1.91 42
16.00 226/0.30 1.00 8.00 1.95 11.80 36.00 1.21 57
25.00 354/0.30 1.20 10.10 2.00 14.70 45.10 0.780 72
35.00 495/0.30 1.20 11.50 2.00 16.20 50.10 0.554 90
50.00 703/0.30 1.40 13.60 2.20 18.30 58.10 0.386 115
70.00 440/0.45 1.40 15.30 2.20 20.00 66.50 0.272 143
95.00 475/0.50 1.60 18.00 2.40 23.50 77.30 0.206 165

Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information