Submersible pump cables
PVC 3 Core Flat Cables PVC 4 Core Flat Cables PVC 3 Core Round Cables more

Submersible pump cables

Applications:

For continuous use in deep well to supply power to submersible pumps down to depths of 500 mtrs.

Construction :

CONDUCTOR PVC INSULATION TOTAL THICKNESS OF DOUBLE PVC SHEATH Conductor Resistance at
20°C
(max) ohms/km
CURRENT
Rating at 40°C
Amps.
Nominal
Area
in
Nos. &
Dia.
of wire
Nominal
Thickness
Nominal
Core
Dia.
Nominal
Thickness
Approx. Overall
Dimensions
Sq. mm. Nos. / mm mm mm mm mm
1.50 22/0.30 0.80 3.25 1.50 10.00 12.10 14
2.50 36/0.30 0.90 3.84 1.50 11.00 7.41 18
4.00 56/0.30 1.00 4.50 1.60 13.00 4.95 26
6.00 85/0.30 1.00 5.30 1.60 14.60 3.30 31
10.00 140/0.30 1.00 6.50 2.00 18.00 1.91 42
16.00 226/0.30 1.00 8.00 2.00 21.20 1.21 57
25.00 354/0.30 1.20 10.10 2.15 26.00 0.780 72
35.00 495/0.30 1.20 11.30 2.15 28.30 0.554 90
50.00 703/0.30 1.40 13.60 2.25 33.50 0.386 115
70.00 440/0.45 1.40 15.30 2.45 37.80 0.272 143
95.00 475/0.50 1.60 18.00 2.40 43.50 0.206 165

Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information