Industrial Cables  
H03VV-F H05VV-F H07RN-F more

Industrial Cables Multi-Core Flexible Cables

680TQ to BS 6007

Application and Description

680TQ to BS 6007 cables are designed for temporary building sites as extension leads for portable or fixed

equipment. The copper braid prevents earth leakage and offers mechanical protection.

Cable Construction

Fine bare copper strands

Stranding to BS 6360 Class 5 or IEC 60228 Class 5

EPR-HOFR( Ethylene Propylene Rubber-Heat and Oil Resistant and Flame Retardant) insulation

CSP(Chlorosulphonated Polyethylene), HOFR (Heat and Oil Resistant and Flame Retardant) bedding

TCWB(tinned copper wire braid)

CSP(Chlorosulphonated Polyethylene), HOFR (Heat and Oil Resistant and Flame Retardant) sheath

680TQ to BS 6007

Core Identification

2 cores: Brown, Blue

3 cores: Green/Yellow, Brown, Blue

4 cores: Green/Yellow, Brown, Black, Grey

5 cores: Green/Yellow, Blue, Brown, Black, Grey

6 cores and above: white insulation with black numerals

Technical Characteristics

Working voltage: 450/750 volts

Minimum bending radius: 8.0xOverall diameter (below 25mm²)

10xOverall diameter (above 25mm²)

Temperature Range: -20º C to +85º C

Flame retardant: IEC 60332.1

Insulation resistance: 20 MΩxkm

Cable Parameter

AWG (No of Strands/ Strand Diameter) No. of Cores x Nominal Cross Sectional Area
#xmm²
Nominal Thickness of Insulation
mm
Nominal Thickness of
Bedding
mm
Diameter of Braid Wire
mm
Nominal Thickness of Sheath
mm
Nominal Overall Diameter
mm
Nominal Weight kg/km
6802TQ
12(56/28) 2x4 1 2 0.2 2.6 19.8 578
6803TQ
12(56/28) 3x4 1 2.2 0.2 2.8 21.3 684
10(84/28) 3x6 1 2.4 0.3 3.1 24.8 955
8(80/26) 3x10 1.2 3.1 0.3 3.8 30.7 1450
6(128/26) 3x16 1.2 3.3 0.3 4 33.8 1840
4(200/26) 3x25 1.4 3.6 0.4 4.4 39.6 2620
6804TQ
12(56/28) 4x4 1 2.3 0.3 3 23.6 874
10(84/28) 4x6 1 2.6 0.3 3.3 27.1 1147
8(80/26) 4x10 1.2 3.3 0.3 4 33.3 1730
6(128/26) 4x16 1.2 3.5 0.4 4.2 37.2 2310
4(200/26) 4x25 1.4 3.8 0.4 4.7 43.2 3170
2(280/26) 4x35 1.4 4.1 0.4 5 47.9 3990
1(400/26) 4x50 1.6 4.6 0.4 5.5 55.1 5320