Airport Cable  

 600/1000V XLPE Insulated, LSZH Sheathed Power Cables (Single Core)

FTX300 1RZ1-R (CU/XLPE/LSZH 600/1000V Single Core)

FTX300 1RZ1-R (CU/XLPE/LSZH 600/1000V Single Core)

APPLICATION

Airprot cables is mainly used in power stations, mass transit underground passenger systems, airports,

petrochemical plants, hotels, hospitals, and high-rise buildings.

STANDARDS

Basic design to IEC 60502-1

FIRE PERFORMANCE

  Flame Retardance (SingleVerticalWireTest) EN60332-1-2; IEC60332-1-2; BSEN 60332-1-2; VDE0482-332-1; NBN C30-004 (cat.F1);NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced FirePropagation(Vertically-mountedbundledwires&cabletest) EN60332-3-24 (cat.C); IEC60332-3-24;BSEN60332-3-24; VDE0482-332-3; NBN C30-004 (cat.F2);NF C32-070- 2.2(C1); CEI 20-22/3-4; EN50266-2-4*;DIN VDE 0482-266- 2-4
  Halogen Free IEC60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;CEI20-37/2-1;BS6425-1*
  NoCorrosive GasEmission IEC60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;CEI20-37/2-2;BS6425-2*
  MinimumSmokeEmission IEC61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;CEI20-37/3-1&2; EN50268-1&2*;BS 7622-1&2*
NoToxic Gases NES02-713;NF C 20-454

Note: Asterisk * denotes superseded standard.

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

Conductor: Plain annealed copper wire, stranded according to IEC 60228 class 2.

Insulation: Extruded cross-linked XLPE compound.

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1.

COLOUR CODE

Insulation Colour: Natural

Sheath Colour: Black (other colors upon request)

Physical AND THERMAL PROPERTIES

Temperature Range During Operation: -30°C ~ 90°C

Temperature Range during Installation : -5°C ~ 50°C

Minimum Bending Radius: 6 x OD

Electrical PROPERTIES

Dielectric Test: 3500 Vr.m.s.x 5’(core/core)

Insulation Resistance: 500 MΩ x km ( at 20°C )

Short circuit Temperature: 250°C ( up to5secs) CONSTRUCTION PARAMETERS

  Cable
Code
Conductor Nominal
Insulation Thickness
Nominal
Overall Diameter
  Approx. Weight
No.of Core XCross Section No./Nominal Diameterof
Strands
  mm2 No./mm mm mm kg/km
FTX300 1RZ1-R1G1.5 1x1.5 7/0.53 0.7 6 48
FTX300 1RZ1-R1G2.5 1x2.5 7/0.67 0.7 6.4 63
FTX300 1RZ1-R1G4 1x4 7/0.85 0.7 7.0 78
FTX300 1RZ1-R1G6 1x6 7/1.04 0.7 7.5 105
FTX300 1RZ1-R1G10 1x10 7/1.35 0.7 8.5 151
FTX300 1RZ1-R1G16 1x16 7/1.70 0.7 9.5 211
FTX300 1RZ1-R1G25 1x25 7/2.14 0.9 11.2 315
FTX300 1RZ1-R1G35 1x35 7/2.52 0.9 12.4 416
FTX300 1RZ1-R1G50 1x50 19/1.78 1.0 14 569
FTX300 1RZ1-R1G70 1x70 19/2.14 1.1 16 792
FTX300 1RZ1-R1G95 1x95 19/2.52 1.1 18 1068
FTX300 1RZ1-R1G120 1x120 37/2.03 1.2 20 1325
FTX300 1RZ1-R1G150 1x150 37/2.25 1.4 22 1627
FTX300 1RZ1-R1G185 1x185 37/2.52 1.6 24.4 2021
FTX300 1RZ1-R1G240 1x240 61/2.25 1.7 27.5 2617
FTX300 1RZ1-R1G300 1x300 61/2.52 1.8 30.3 3252
FTX300 1RZ1-R1G400 1x400 61/2.85 2.0 33.9 4131
FTX300 1RZ1-R1G500 1x500 61/3.20 2.2 37.6 5175
FTX300 1RZ1-R1G630 1x630 127/2.52 2.4 42.4 6631
FTX300 1RZ1-R1G800 1x800 127/2.85 2.6 47.3 8412
FTX300 1RZ1-R1G1000 1x1000 127/3.20 2.8 52.4 10530

Electrical PROPERTIES

Conductor Operating Temperature : 90°C

Ambient Temperature : 30°C

Current-Carrying Capacities (Amp)

 Conductor
cross- sectional area
Reference
Method4
(enclosed inconduitin thermally
insulating
walletc)
Reference
Method3
(enclosed inconduitona
wallorin
trunkingetc)
 Reference
Method1
(clipped
direct)
 Reference
Method11
(onaperforated cabletray,
horizontal
orvertical)
Reference
Method 12 (freeair)
 Horizontalflat spaced  Verticalflat spaced   Trefoil

 2
cables, single- phase
a.c.ord.c.
 3 or 4cables, 3-phasea.c.  2cables, single- phase a.c.ord.c  3 or 4cables, 3-phasea.c.  2cables, single- phase
a.c.or
d.c. flat
and
touching
 3 or 4cables, 3-phase
a.c. flat
and
touching or trefoil
 2cables,
single- phase
a.c.or
d.c.orflat and touching
 3 or 4cables, 3-phase
a.c. flat
and
touching or trefoil
 2cables, single- phase a.c.ord.c.or 3cablesthree phase

2
cables, single- phase
a.c.ord.c.or 3
cables three phase

 3cables, trefoil
3-phasea.c.
1 2 3 4 5 6 7 8 9 10 11 12
mm2 A A A A A A A A A A A
1.5 18 17 22 19 25 23 - - - - -
2.5 24 23 30 26 34 31 - - - - -
4 33 30 40 35 46 41 - - - - -
6 43 39 51 45 59 54 - - - - -
10 58 53 71 63 81 74 - - - - -
16 76 70 95 85 109 99 - - - - -
25 100 91 126 111 143 130 158 140 183 163 138
35 125 111 156 138 176 161 195 176 226 203 171
50 149 135 189 168 228 209 293 215 274 246 209
70 189 170 240 214 293 268 308 279 351 318 270
95 228 205 290 259 355 326 375 341 426 389 330
120 263 235 336 299 413 379 436 398 495 453 385
150 300 270 375 328 476 436 505 461 570 524 445
185 341 306 426 370 545 500 579 530 651 600 511
240 400 358 500 433 644 590 686 630 769 711 606
300 459 410 573 493 743 681 794 730 886 824 701
400 - - 684 584 868 793 915 849 1065 994 820
500 - - 783 666 990 904 1044 973 1228 1150 936
630 - - 900 764 1130 1033 1191 1115 1423 1338 1069
800 - - - - 1288 1179 1358 1275 1580 1485 1214
1000 - - - - 1443 1323 1520 1436 1775 1671 1349
Voltage Drop (Per Amp Per Meter)
 Sizeof
conductor
 2 cables d.c. 2cables,single-phasea.c. 3or 4cables,3-phase a.c.
 Ref.
Methods3
and 4(enclosedin
conduitetc, inoron a wall)
 Ref.
Methods1
and11(clipped
director ontray
stouching)
 Ref.
Methods3
and 4(enclosed
inconduitetc,
inoron a wall)
 Ref.
Methods1,11 and12 (intrefoil)
 Ref.
Methods1
and11
(Flat and touching)
1 2 3 4 5 6 7
mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
1.5 31 31 27 27 27 27
2.5 19 19 16 16 16 16
4 33 12 10 10 10 10
6 7.8 7.9 6.8 6.8 6.8 6.8
10 4.7 4.7 4.7 4 4 4
16 2.9 2.9 2.9 2.5 2.5 2.5

 

 

r x z r x z r x z r x z r x z
25 1.85 1.85 0.31 1.90 1.85 0.190 1.85 1.60 0.27 1.65 1.600 0.165 1.600 1.600 0.190 1.600
35 1.35 1.35 0.29 1.35 1.35 0.180 1.35 1.15 0.25 1.15 1.150 0.155 1.50 1.150 0.180 1.150
50 0.99 1.00 0.29 1.05 0.99 0.180 1.00 0.87 0.25 0.90 0.860 0.155 0.870 0.860 0.180 0.870
70 0.68 0.70 0.28 0.75 0.68 0.175 0.71 0.60 0.24 0.65 0.590 0.150 0.610 0.590 0.175 0.620
95 0.49 0.51 0.27 0.58 0.49 0.170 0.52 0.44 0.23 0.50 0.430 0.145 0.450 0.430 0.170 0.460
120 0.39 0.41 0.26 0.48 0.39 0.165 0.43 0.35 0.23 0.42 0.340 0.140 0.370 0.340 0.165 0.380
150 0.32 0.33 0.26 0.43 0.32 0.165 0.36 0.29 0.23 0.37 0.280 0.140 0.310 0.280 0.165 0.320
185 0.25 0.27 0.26 0.37 0.26 0.165 0.30 0.23 0.23 0.32 0.220 0.140 0.260 0.220 0.165 0.280
240 0.19 0.21 0.26 0.33 0.20 0.160 0.25 0.185 0.22 0.29 0.170 0.140 0.220 0.170 0.165 0.240
300 0.155 0.175 0.25 0.31 0.16 0.160 0.22 0.150 0.22 0.27 0.140 0.140 0.195 0.135 0.160 0.210
400 0.12 0.140 0.25 0.29 0.13 0.155 0.20 0.125 0.22 0.25 0.110 0.135 0.175 0.110 0.160 0.195
500 0.093 0.120 0.25 0.28 0.105 0.155 0.185 0.100 0.22 0.24 0.090 0.135 0.160 0.088 0.160 0.180
630 0.072 0.100 0.25 0.27 0.086 0.155 0.175 0.088 0.21 0.23 0.074 0.135 0.150 0.071 0.160 0.170
800 0.056 - - - 0.072 0.150 0.170 - - - 0.062 0.130 0.145 0.059 0.155 0.165
1000 0.045 - - - 0.063 0.150 0.165 - - - 0.055 0.130 0.140 0.050 0.155 0.165
Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance