Airport Cable  
 

Airport Cable

Airfield Lighting Cables

400Hz Cables

Split Concentric Halogen Free 400Hz Airport Cable

 

 

 

 

Applications

Split Concentric Halogen Free 400Hz Airport Cables are designed for 400 Hz systems for power supply of

aircraft, computer systems and radar stations, suitable for laying in earth, in water, outdoors, indoors and in

cable ducts.

Construction

Conductor: Stranded copper conductor, Class 6 /Class 5 to VDE 0295/IEC 60228.

Insulation: TP rubber.

Control Core: 1mm² stranded copper conductor with XLPE insulation.

Cable Assembling: Helical concentric stranding of bare neutral conductors and control wire separated by

dummies.

Sheath: 2 layer PUR.

Standards

VDE 0295

Split Concentric Halogen Free 400Hz Airport Cable

Technical Data

Rated Voltage Uo/U (Um) :600/1000V

Operating Temperatures :-40℃~+85℃

Minimum Bending Radius :static: 6×OD; dynamic: 8×OD

Flame Retardant :Yes

Abrasion Resistant :Yes

UV Resistant :Yes

Oil Resistant :Yes

Dimensions and Weight

Construction Nominal Diameter Over Insulation Nominal Diameter of Control Core Nominal Diameter Under Sheath Nominal Overall Diameter Nominal
Weight
No. ×mm² mm mm mm mm kg/km
1×70+10×2.5+8×1 13.8 2.1 17.8 22.2 1300

Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information