| Airport Cable | |||
Airport Cable
Airfield Lighting Cables
Primry Circuit Cables
RHZ1
Applications
RHZ1 Airprot cables are used as airfield lighting equipment primary cables for the series circuit connecting the
Constant Current Regulators and the isolating transformers, and between the isolating transformers.
Construction
Conductor: Stranded copper conductor.
Inner Semi-Conductor: Extruded semi-conducting compound.
Insulation: XLPE.
Outer Semi-Conductor: Extruded semi-conducting compound.
Shield: Copper tape shield.
Outer Sheath: Polyolefin.
Standards
UNE 21161-93 (Spain)

Technical Data
Rated Voltage Uo/U (Um) :6/10kV
Maximum Conductor Temperature :90℃
Short Circuit Temperature :250℃
Operating Temperatures :-20℃~+90℃
Minimum Bending Radius :18×OD
Halogen Free :Yes
No Corrosive & Toxic Gases :Yes
Low Smoke :Yes
Flame Retardant :Yes
Impacted Resistant :Yes
Weather Resistant :Yes
Oil Resistant :Yes
Dimensions and Weight
| Construction | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Nominal Weight |
|---|---|---|---|---|
| No. ×mm² | mm | mm | mm | kg/km |
| 1×6 | 3.5 | 2.0 | 18.0 | 400 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information