| Airport Cable | |||
Indoor Feeder Cables
600/1000V XLPE Insulated, LSZH Sheathed, Armoured Power Cables (Single Core)
FTX300 1RZ1MZ1-R (CU/XLPE/LSZH/AWA/LSZH 600/1000V Class 2)

APPLICATION
600/1000V XLPE Insulated, LSZH Sheathed, Armoured Power Cables (Single Core) are mainly used in
power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals,
and high-rise buildings.
STANDARDS
Basic design to BS 6724
FIRE PERFORMANCE
| FlameRetardance (SingleVerticalWireTest) | EN60332-1-2; IEC60332-1-2; BSEN 60332-1-2; VDE0482-332-1; NBN C30-004 (cat.F1);NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
|---|---|
| Reduced FirePropagation(Vertically-mountedbundledwires &cabletest) | EN60332-3-24 (cat.C); IEC60332-3-24;BSEN60332-3-24;VDE0482-332-3;NBN C30-004 (cat.F2);NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
| Halogen Free | IEC60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;CEI20-37/2-1;BS6425-1* |
| NoCorrosive GasEmission | IEC60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;CEI20-37/2-2;BS6425-2* |
| MinimumSmokeEmission | IEC61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;CEI20-37/3-1&2; EN50268-1&2*;BS 7622-1&2* |
| NoToxic Gases | NES02-713;NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
600/1000V CABLE CONSTRUCTION
Conductor : Plain annealed copper wire, stranded according to IEC 60228 class 2.
Insulation: Extruded cross-linked XLPE compound.
Inner sheath : LSZH Compound
Armouring : Aluminium Wire
Outer Sheath : Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1.
COLOUR CODE
Insulation Colour : Natural
Sheath Colour : Black (other colors upon request)
Physical AND THERMAL PROPERTIES
Temperature Range During Operation: -30°C ~ 90°C
Temperature Range during Installation : -5°C ~ 50°C
Minimum Bending Radius: 8 x OD
Electrical PROPERTIES
Dielectric Test:3500 Vr.m.s.x 5’(core/core)
Insulation Resistance:500 MΩ x km ( at 20°C )
Short circuit Temperature:250°C ( up to5secs)
CONSTRUCTION PARAMETERS
| Cable Code | Conductor | Diameter Under Armour |
Armour Wire Diameter | Nominal Overall Diameter |
Approx. Weight | |
|---|---|---|---|---|---|---|
| No. of CoreX
Cross Section |
No. /Nominal Diameter of Strands |
|||||
|
mm2 | No./mm | mm | mm | mm | kg/km |
| FTX300 1RZ1MZ1-R1G70 | 1x70 | 19/2.14 | 15.4 | 1.25 | 21.5 | 960 |
| FTX300 1RZ1MZ1-R1G95 | 1x95 | 19/2.52 | 17.3 | 1.25 | 23.4 | 1240 |
| FTX300 1RZ1MZ1-R1G120 | 1x120 | 37/2.03 | 19.1 | 1.6 | 25.9 | 1650 |
| FTX300 1RZ1MZ1-R1G150 | 1x150 | 37/2.25 | 21.1 | 1.6 | 27.9 | 1970 |
| FTX300 1RZ1MZ1-R1G185 | 1x185 | 37/2.52 | 23.2 | 1.6 | 30.1 | 2390 |
| FTX300 1RZ1MZ1-R1G240 | 1x240 | 61/2.25 | 26.2 | 1.6 | 33.2 | 3040 |
| FTX300 1RZ1MZ1-R1G300 | 1x300 | 61/2.52 | 28.8 | 1.6 | 35.8 | 3790 |
| FTX300 1RZ1MZ1-R1G400 | 1x400 | 61/2.85 | 32.7 | 2.0 | 40.9 | 4790 |
| FTX300 1RZ1MZ1-R1G500 | 1x500 | 61/3.20 | 36.2 | 2.0 | 44.6 | 5880 |
| FTX300 1RZ1MZ1-R1G630 | 1x630 | 127/2.52 | 40.6 | 2.0 | 49.2 | 7400 |
| FTX300 1RZ1MZ1-R1G800 | 1x800 | 127/2.85 | 45.7 | 2.5 | 55.7 | 9500 |
| FTX300 1RZ1MZ1-R1G1000 | 1x1000 | 127/3.20 | 50.6 | 2.5 | 61.0 | 11750 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information
Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
|
Conductor cross- sectional area |
Reference Method1 (clipped direct) |
Reference Method11(ona perforated horizontal cable trayor Reference Method 13 [freeair]) |
Reference Method 12(free air) |
Insingle- wayducts |
Laiddirectin ground |
||||
|---|---|---|---|---|---|---|---|---|---|
|
2 cables, single- phase a.c.ord.c. | 3 or 4cables, 3-phasea.c. | 2 cables, single- phase a.c.ord.c. | 3 or 4cables, 3-phasea.c. | 3cables 3-phase a.c.trefoiltouching | 2 cables, single- phase a.c.ord.c. | 3 or 4cables, 3-phasea.c. | 2 cables, single- phase a.c.ord.c. | 3 or 4cables, 3-phasea.c. |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
| mm2 | A | A | A | A | A | A | A | A | A |
| 70 | 303 | 277 | 322 | 293 | 285 | 310 | 280 | 340 | 290 |
| 95 | 367 | 333 | 389 | 352 | 346 | 365 | 330 | 405 | 345 |
| 120 | 425 | 383 | 449 | 405 | 402 | 410 | 370 | 460 | 389 |
| 150 | 488 | 437 | 516 | 462 | 463 | 445 | 405 | 510 | 435 |
| 185 | 557 | 496 | 587 | 524 | 529 | 485 | 440 | 580 | 490 |
| 240 | 656 | 579 | 689 | 612 | 625 | 550 | 500 | 670 | 560 |
| 300 | 755 | 662 | 792 | 700 | 720 | 610 | 550 | 750 | 630 |
| 400 | 853 | 717 | 899 | 767 | 815 | 640 | 580 | 830 | 700 |
| 500 | 962 | 791 | 1016 | 851 | 918 | 690 | 620 | 910 | 770 |
| 630 | 1082 | 861 | 1146 | 935 | 1027 | 750 | 670 | 1000 | 840 |
| 800 | 1170 | 904 | 1246 | 987 | 1119 | 828 | 735 | 1117 | 931 |
| 1000 | 1261 | 961 | 1345 | 1055 | 1214 | 919 | 811 | 1254 | 1038 |
|
Conductor cross-section alarea |
2 cablesd.c. | 2 cablessingle-phase a.c. | 3 or 4 cables three-phase a.c. |
2 cables single phasea.c. |
3 or 4 cables, 3-phase a.c.touching |
|||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Reference Method 1 & 11 (touching) | Reference Method1,
11
& 12 (intrefoil touching) |
Reference Method1&11
(Flat touching) |
In ducts |
In ground |
In ducts | In ground | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | ||||||
| mm2 | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | ||||||
|
|
r | x | z | r | x | z | r | x | z |
|
|
|
|
| 70 | 0.67 | 0.68 | 0.20 | 0.71 | 0.59 | 0.17 | 0.62 | 0.6 | 0.25 | 0.65 | 0.80 | 0.70 | 0.70 | 0.61 |
| 95 | 0.49 | 0.51 | 0.195 | 0.55 | 0.44 | 0.17 | 0.47 | 0.46 | 0.24 | 0.52 | 0.65 | 0.53 | 0.56 | 0.46 |
| 120 | 0.39 | 0.41 | 0.190 | 0.45 | 0.35 | 0.165 | 0.39 | 0.38 | 0.24 | 0.44 | 0.55 | 0.43 | 0.48 | 0.37 |
| 150 | 0.31 | 0.33 | 0.185 | 0.38 | 0.29 | 0.160 | 0.33 | 0.31 | 0.23 | 0.39 | 0.50 | 0.37 | 0.43 | 0.32 |
| 185 | 0.25 | 0.27 | 0.185 | 0.33 | 0.23 | 0.160 | 0.28 | 0.26 | 0.23 | 0.34 | 0.45 | 0.31 | 0.39 | 0.27 |
| 240 | 0.195 | 0.21 | 0.180 | 0.28 | 0.18 | 0.155 | 0.24 | 0.21 | 0.22 | 0.30 | 0.40 | 0.26 | 0.35 | 0.23 |
| 300 | 0.155 | 0.17 | 0.175 | 0.25 | 0.145 | 0.150 | 0.21 | 0.17 | 0.22 | 0.28 | 0.37 | 0.24 | 0.32 | 0.21 |
| 400 | 0.115 | 0.145 | 0.170 | 0.22 | 0.125 | 0.150 | 0.195 | 0.160 | 0.21 | 0.27 | 0.35 | 0.21 | 0.30 | 0.19 |
| 500 | 0.093 | 0.125 | 0.170 | 0.21 | 0.105 | 0.145 | 0.180 | 0.145 | 0.20 | 0.25 | 0.33 | 0.20 | 0.28 | 0.18 |
| 630 | 0.073 | 0.105 | 0.165 | 0.195 | 0.092 | 0.145 | 0.170 | 0.135 | 0.195 | 0.24 | 0.30 | 0.19 | 0.26 | 0.17 |
| 800 | 0.056 | 0.090 | 0.160 | 0.190 | 0.086 | 0.140 | 0.165 | 0.130 | 0.180 | 0.23 | 0.28 | 0.18 | 0.24 | 0.16 |
| 1000 | 0.045 | 0.092 | 0.155 | 0.180 | 0.080 | 0.135 | 0.155 | 0.125 | 0.170 | 0.21 | 0.26 | 0.17 | 0.22 | 0.15 |
r = conductor resistance at operating temperature
x = reactance
z = impedance