Airport Cable  
 

  Airport Cable

Airfield Lighting Cables

Primry Circuit Cables

C 33-224 / C33-225    

 

 

 

Applications

C 33-224 / C33-225 Airport cables are used as airfield lighting equipment primary cables for the series circuit

connecting the Constant Current Regulators and the isolating transformers, and between the isolating

transformers.

Construction

Conductor: Stranded bare or tinned copper conductor.

Inner Semi-Conductor: Extruded semi-conducting compound.

Insulation: XLPE. EPDM can be offered upon request.

Outer Semi-Conductor: Extruded semi-conducting compound.

Shield: Copper tape shield. Copper wire shield can be offered upon request.

Sheath: XLPE. PVC/HFFR/CR can be offered upon request.

Standards

C33-224

C33-225

C 33-224 / C33-225

Technical Data

Rated Voltage Uo/U (Um) :3.6/6 (7.2kV); 6/10 (12kV)

Maximum Conductor Temperature :90℃

Short Circuit Temperature :250℃

Operating Temperatures :-20℃~+70℃

Minimum Bending Radius :static: 10×OD; dynamic: 20×OD

Impacted Resistant :Yes

Weather Resistant :Yes

Dimensions and Weight

3.6/6 (7.2kV)

Construction No. of Strand Nominal Insulation Thickness Nominal Sheath Thickness Nominal Overall Diameter Nominal Weight
No. ×mm² - mm mm mm kg/km
1×6 7 2.7 1.4 12.5 198

6/10 (12kV)

Construction No. of Strand Nominal Insulation Thickness Nominal Sheath Thickness Nominal Overall
Diameter
Nominal Weight
No. ×mm² - mm mm mm kg/km
1×6 7 3.6 1.6 14.7 250

Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information