| Windmill Cables | |||
| EPR/HFXLEVA LSOH 0.6/1kV Torsion Resistant Power Cable | HFEPR/HFEVA 0.6/1kV LSOH Screened Torsion Resistant Power Cable | Al Conductor EPR/XLEVA 0.6/1kV LSOH Power Cable 90℃ | more |
Windmill Cables
NA2XS(F)2Y RE/RM Medium Voltage Power Cable
Application
NA2XS(F)2Y RE/RM Medium Voltage Power Cables are commonly used in wind turbines, suitable for indoor
installation and in cable ducts, outdoors, underground and in water.
Standards
IEC 60502-2
DIN VDE 0276 part 620
Construction
2Y.jpg)
Conductor: Circular solid (RE) or stranded (RM) aluminium conductor.
Conductor Screen: Semiconducting compound.
Insulation: XLPE.
Insulation Screen: Semiconducting compound.
Tape: Semiconducting swellable tape.
Screen: Braiding of copper wires with copper tape.
Tape: Separation tape.
Sheath: PE.
Technical Data
Rated Voltage Uo/U (Um):6/10 kV, 12/20 kV, 18/30 kV
Operating Temperatures:-40℃~+90℃
Minimum Bending Radius:15×OD
Short-circuit Temperature:250℃
Longitudinally Water-Tight:Yes
Halogen Free:Yes
Dimensions and Weight
6/10 kV
| Construction | Nominal Overall Diameter | Nominal Weight |
|---|---|---|
| No. of cores×mm² | mm | kg/km |
| 1×70 re | 26.5 | 760 |
| 1×95 re | 26.5 | 860 |
| 1×120 re | 28.5 | 930 |
| 1×150 re | 29.5 | 1130 |
| 1×185 re | 31.5 | 1230 |
| 1×240 re | 33.5 | 1470 |
| 1×300 re | 36.5 | 1670 |
| 1×400 re | 40.5 | 2060 |
| 1×500 re | 43.5 | 2400 |
| 1×630 re | 45.5 | 2790 |
| 1×800 re | 49.5 | 3340 |
| 1×1000 re | 53.5 | 4000 |
| 1×35 rm | 25.5 | 600 |
| 1×50 rm | 26.5 | 670 |
| 1×70 rm | 28.5 | 770 |
| 1×95 rm | 29.0 | 880 |
| 1×120 rm | 31.0 | 950 |
| 1×150 rm | 32.0 | 1150 |
| 1×185 rm | 34.0 | 1250 |
| 1×240 rm | 36.0 | 1500 |
| 1×300 rm | 38.5 | 1700 |
| 1×400 rm | 42.5 | 2100 |
| 1×500 rm | 45.5 | 2450 |
| 1×630 rm | 47.5 | 2850 |
| 1×800 rm | 52.5 | 3490 |
| 1×1000 rm | 56.5 | 4080 |
12/20 kV
| Construction | Nominal Overall Diameter | Nominal Weight |
|---|---|---|
| No. of cores×mm² | mm | kg/km |
| 1×70 re | 30.5 | 910 |
| 1×95 re | 31.5 | 1030 |
| 1×120 re | 32.5 | 1130 |
| 1×150 re | 33.5 | 1320 |
| 1×185 re | 35.5 | 1470 |
| 1×240 re | 38.5 | 1720 |
| 1×300 re | 40.5 | 1960 |
| 1×400 re | 43.5 | 2300 |
| 1×500 re | 46.5 | 2740 |
| 1×630 re | 49.5 | 3070 |
| 1×800 re | 53.5 | 3680 |
| 1×1000 re | 57.5 | 4360 |
| 1×50 rm | 30.5 | 820 |
| 1×70 rm | 32.5 | 930 |
| 1×95 rm | 33.5 | 1050 |
| 1×120 rm | 35.0 | 1150 |
| 1×150 rm | 36.0 | 1350 |
| 1×185 rm | 38.0 | 1500 |
| 1×240 rm | 41.0 | 1750 |
| 1×300 rm | 43.0 | 2000 |
| 1×400 rm | 46.0 | 2350 |
| 1×500 rm | 49.0 | 2800 |
| 1×630 rm | 51.5 | 3140 |
| 1×800 rm | 57.5 | 3840 |
| 1×1000 rm | 60.5 | 4460 |
18/30 kV
| Construction | Nominal Overall Diameter | Nominal Weight |
|---|---|---|
| No. of cores×mm² | mm | kg/km |
| 1×70 re | 34.5 | 1180 |
| 1×95 re | 35.5 | 1320 |
| 1×120 re | 37.5 | 1420 |
| 1×150 re | 38.5 | 1670 |
| 1×185 re | 40.5 | 1810 |
| 1×240 re | 42.5 | 2010 |
| 1×300 re | 45.5 | 2300 |
| 1×400 re | 48.5 | 2740 |
| 1×500 re | 51.5 | 3140 |
| 1×630 re | 55.5 | 3480 |
| 1×800 re | 59.5 | 4100 |
| 1×1000 re | 63.5 | 4800 |
| 1×50 rm | 35.0 | 1100 |
| 1×70 rm | 37.0 | 1200 |
| 1×95 rm | 38.0 | 1350 |
| 1×120 rm | 40.0 | 1450 |
| 1×150 rm | 41.0 | 1700 |
| 1×185 rm | 43.0 | 1850 |
| 1×240 rm | 45.0 | 2050 |
| 1×300 rm | 48.0 | 2350 |
| 1×400 rm | 51.0 | 2800 |
| 1×500 rm | 54.0 | 3200 |
| 1×630 rm | 57.5 | 3570 |
| 1×800 rm | 62.5 | 4280 |
| 1×1000 rm | 66.5 | 4970 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information