Windmill Cables
EPR/HFXLEVA LSOH 0.6/1kV Torsion Resistant Power Cable HFEPR/HFEVA 0.6/1kV LSOH Screened Torsion Resistant Power Cable Al Conductor EPR/XLEVA 0.6/1kV LSOH Power Cable 90℃ more

  Windmill Cables

NA2XS(F)2Y RE/RM Medium Voltage Power Cable

Application

NA2XS(F)2Y RE/RM Medium Voltage Power Cables are commonly used in wind turbines, suitable for indoor

installation and in cable ducts, outdoors, underground and in water.

Standards

IEC 60502-2

DIN VDE 0276 part 620

Construction

NA2XS(F)2Y RE/RM Medium Voltage Power Cable

Conductor: Circular solid (RE) or stranded (RM) aluminium conductor.

Conductor Screen: Semiconducting compound.

Insulation: XLPE.

Insulation Screen: Semiconducting compound.

Tape: Semiconducting swellable tape.

Screen: Braiding of copper wires with copper tape.

Tape: Separation tape.

Sheath: PE.

Technical Data

Rated Voltage Uo/U (Um):6/10 kV, 12/20 kV, 18/30 kV

Operating Temperatures:-40℃~+90℃

Minimum Bending Radius:15×OD

Short-circuit Temperature:250℃

Longitudinally Water-Tight:Yes

Halogen Free:Yes

Dimensions and Weight

6/10 kV

Construction Nominal Overall Diameter Nominal Weight
No. of cores×mm² mm kg/km
1×70 re 26.5 760
1×95 re 26.5 860
1×120 re 28.5 930
1×150 re 29.5 1130
1×185 re 31.5 1230
1×240 re 33.5 1470
1×300 re 36.5 1670
1×400 re 40.5 2060
1×500 re 43.5 2400
1×630 re 45.5 2790
1×800 re 49.5 3340
1×1000 re 53.5 4000
1×35 rm 25.5 600
1×50 rm 26.5 670
1×70 rm 28.5 770
1×95 rm 29.0 880
1×120 rm 31.0 950
1×150 rm 32.0 1150
1×185 rm 34.0 1250
1×240 rm 36.0 1500
1×300 rm 38.5 1700
1×400 rm 42.5 2100
1×500 rm 45.5 2450
1×630 rm 47.5 2850
1×800 rm 52.5 3490
1×1000 rm 56.5 4080

12/20 kV

Construction Nominal Overall Diameter Nominal Weight
No. of cores×mm² mm kg/km
1×70 re 30.5 910
1×95 re 31.5 1030
1×120 re 32.5 1130
1×150 re 33.5 1320
1×185 re 35.5 1470
1×240 re 38.5 1720
1×300 re 40.5 1960
1×400 re 43.5 2300
1×500 re 46.5 2740
1×630 re 49.5 3070
1×800 re 53.5 3680
1×1000 re 57.5 4360
1×50 rm 30.5 820
1×70 rm 32.5 930
1×95 rm 33.5 1050
1×120 rm 35.0 1150
1×150 rm 36.0 1350
1×185 rm 38.0 1500
1×240 rm 41.0 1750
1×300 rm 43.0 2000
1×400 rm 46.0 2350
1×500 rm 49.0 2800
1×630 rm 51.5 3140
1×800 rm 57.5 3840
1×1000 rm 60.5 4460

18/30 kV

Construction Nominal Overall Diameter Nominal Weight
No. of cores×mm² mm kg/km
1×70 re 34.5 1180
1×95 re 35.5 1320
1×120 re 37.5 1420
1×150 re 38.5 1670
1×185 re 40.5 1810
1×240 re 42.5 2010
1×300 re 45.5 2300
1×400 re 48.5 2740
1×500 re 51.5 3140
1×630 re 55.5 3480
1×800 re 59.5 4100
1×1000 re 63.5 4800
1×50 rm 35.0 1100
1×70 rm 37.0 1200
1×95 rm 38.0 1350
1×120 rm 40.0 1450
1×150 rm 41.0 1700
1×185 rm 43.0 1850
1×240 rm 45.0 2050
1×300 rm 48.0 2350
1×400 rm 51.0 2800
1×500 rm 54.0 3200
1×630 rm 57.5 3570
1×800 rm 62.5 4280
1×1000 rm 66.5 4970

Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information