TUNNEL CABLES |
||||||||||
TUNNEL CABLES
NTSKCGEWöU
Application
For the connection of mobile electrical equipment in mines and tunnels. Suitable also for coal cutting machines,
particularly for extreme bending loads inside of steel or plastic track chains.
CABLE CONSTRUCTION
Power Cores
conductor:Tinned copper conductor DIN VDE 0295 class 5
Insulation:Based on 3Gl3-EPR rubber and semi rubber compound
CONTROL CORES+MONITORING PE CORE(S)
conductor:Tinned copper conductor DIN VDE 0295 class 5
Insulation:3Gl3 type EPR compound and semi conductive rubber compound
Cradle Separator:A shaped section of elastomeric material. Semi conductive, with control wire in the center.
designed to support the core assembly. fill the center interstice and provide a specified separation between
individual power cores
Electrical Field Control:Inner and Outer semiconductive layer of semiconductive rubber
Core Identification:Power cores naturally colored. Control cores blue colored
Lay Up:Three main conductors laid-up with three control cores & PE conductors in interstice over a cradle
separator.
Inner Sheath:GM1b Type EPR compound
Screen / Armour:Flexible- pliable armour in helix of tinned copper and galvanised steel wires
Outer Sheath:5GM5 Type elastomer compound. Red
STANDARDS

| construction | DIN VDE 0250-813 |
|---|---|
General Requirements |
DIN VDE 0250-1 |
Guide Use |
DIN VDE 0298-3 |
Electrical Tests |
DIN VDE 0472-501, 503, 508 |
Non-Electrical Tests |
DIN VDE 0472-401. 402,602,303, 615 |
Under Fire Condition Tests |
DIN VDE 0472-803, 804 |
Flame Retardant |
VDE 0482-332-1-2,DIN EN 60332-1-2,IEC 60332-1 |
Oil Resistant |
HD/EN/IEC 60811-2-1.,DIN VDE0473-811-2-1 |
Technical Characteristics
| Rated Voltage | 1.8/3 KV |
3.6/6 KV |
|---|---|---|
AC Test Voltage |
6KV |
11KV |
Max.Permissible Operating Voltage AC |
2.1/3.6 KV |
4.2/7.2 KV |
Max.Permissible Operating Voltage DC |
2.7/5.4 KV |
5.4/10.8 KV |
Min Bending Radius |
DIN VDE 0298-3 |
|
Current Carrying Capacity |
DIN VDE 0298-4 |
|
Working Temperature |
||
Fixed |
-40°C-+80°C |
|
Mobile |
-25°C-+80°C |
|
Dimensions And Weight
1.8/3 KV
| Cross Section (mm²) | Overall Diameter |
conductor Resistance at 20°C (Ω/km) |
Appro. Weight (kg/km) |
|---|---|---|---|
3x25+3×(1.5 ST KON+ |
42.1-45.3 |
0.795 |
3190 |
3x35+3×(1.5 ST KON+ |
46.5-49.7 |
0.565 |
3920 |
3x50+3×(1.5 ST KON+ |
50.4-53.5 |
0.393 |
4730 |
3x70+3×(1.5 ST KON+ |
55.8-60.0 |
0.277 |
6070 |
3x95+3×(1.5 ST KON+ |
61.5-65.7 |
0.21 |
7620 |
3x120+3×(1.5 ST KON+ |
66.0-70.3 |
0.164 |
9270 |
3x150+3×(1.5 ST KON+ |
71.8-76.0 |
0.132 |
10920 |
3x185+3×(1.5 ST KON+ |
76.2-80.3 |
0.108 |
12770 |
3x240+3×(1.5 ST KON+ |
84.1-89.4 |
0.0817 |
15860 |
1.8/3 KV
| Cross Section (mm²) | Overall Diameter |
conductor Resistance at 20°C (Ω/km) |
Appro. Weight (kg/km) |
|---|---|---|---|
3x35+3×(1.5 ST KON+ |
46.0-51.0 |
0.554 |
3960 |
3x50+3×(1.5 ST KON+ |
51.0-55.0 |
0.368 |
4980 |
3x70+3×(1.5 ST KON+ |
57.0-62.0 |
0.272 |
6360 |
3x95+3×(1.5 ST KON+ |
64.0-69.0 |
0.206 |
8150 |
3x50+3×(35+35/3KON) |
66.0-71.0 |
0.368 |
8390 |
3x70+3×(50+50/3KON) |
74.0-79.0 |
0.272 |
10350 |
3x95+3×(70+70/3KON) |
85.0-90.0 |
0.206 |
13340 |
3.6/6 KV
| Cross Section (mm²) | Overall Diameter |
conductor |
Appro. Weight (kg/km) |
|---|---|---|---|
3x25+3×(1.5 ST KON+ |
47.3-50.4 |
0.795 |
3710 |
3x35+3×(1.5 ST KON+ |
50.2-53.4 |
0.565 |
4320 |
3x50+3×(1.5 ST KON+ |
53.5-57.7 |
0.393 |
5250 |
3x70+3×(1.5 ST KON+ |
59.6-63.8 |
0.277 |
6600 |
3x95+3×(1.5 ST KON+ |
64.3-68.5 |
0.21 |
8030 |
3x120+3×(1.5 ST KON+ |
70.7-74.8 |
0.164 |
9990 |
3x150+3×(1.5 ST KON+ |
74.5-78.8 |
0.132 |
11330 |
3x185+3×(1.5 ST KON+ |
78.5-93.0 |
0.108 |
13280 |
3x240+3×(1.5 ST KON+ |
86.8-92.1 |
0.0817 |
16380 |
3.6/6 KV
| Cross Section (mm²) | Overall Diameter min-max |
conductor Resistance at 20°c |
Appro. Weight (kg/km) |
|---|---|---|---|
3x35+3×(1.5 ST KON+ 25/3 |
46.0-51.0 |
0.554 |
3960 |
3x50+3×(1.5 ST KON+ 25/3 |
51.0-55.0 |
0.368 |
4980 |
3x70+3×(1.5 ST KON+ 35/3 |
57.0-62.0 |
0.272 |
6360 |
3x95+3×(1.5 ST KON+ 50/3 KON)+ÜL KON |
64.0-69.0 |
0.206 |
8150 |
3x35+3x(35+35/3KON) +2x(0.75ST KON)+1x(2x0.75ÜL KON) |
69.0-74.0 |
0.554 |
7800 |
3x50+3x(50+50/3KON) +2x(0.75ST |
73.0-78.0 |
0.368 |
9340 |
3x70+3x(70+70/3KON) +2x(0.75ST |
80.0-85.0 |
0.272 |
11580 |
3x95+3x(95+95/3KON) +2x(0.75ST KON)+1x(2x0.75ÜL KON) |
89.0-94.0 |
0.206 |
13930 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information