A-2Y(L)2YB2Y S(H45)

A-2Y(L)2YB2Y S(H45)

Application

The cables are designed for transmission of low frequent signals up to 90 KHz through symmetric circuits in

railway networks, and are suitable for laying directly into the ground or in ducts.

Standards

Dlk 1.013.109y

Dlk 1.013.110y

Construction

Conductors: Solid Annealed copper, 0.9 or 1.4 mm nominal diameter.

Insulation: Solid polyethylene.

Cabling Element: Four insulated conductors are twisted together to form a quad.

Stranding: Quads are helically stranded in concentric layers. Cables from 7 quads on, have two extra conductors

of 0.5mm with perforated insulation (surveillance conductors).

Core Wrapping: Plastic tape(s) with overlapping.

IMoisture Barrier: One laminated sheath made of aluminium tape (0.15mm) coated with PE-Copolymer on at

least one side is applied with longitudinally overlap.

Inner Sheath: Low density polyethylene.

Electromagnetic Shield: One helically applied steel tape (0.2-0.3mm) or two helically applied steel tapes (0.1mm).

Outer Sheath: Low density polyethylene.

Type Codes

A– outdoor cable

2Y- solid PE conductor insulation

(L)2Y- inner laminated PE sheath

B- steel tape armor

2Y- PE outer sheath

S- signal cable

LG- layer stranding

H(n)- operating capacity

Ring marking of Quad

The single core is identifi ed by black ring markings:

Side Circuit 1: a-wire, without marking

b-wire, 1 mark distance 17mm

Side Circuit 2: a-wire, 2 marks distance 34mm

b-wire, 2 marks distance 17mm

Electrical Characteristics at 20℃

Nominal Conductor Diameter mm 0.9 1.4
Maximum Conductor Resistance Ω/km 56.6 23.4
Minimum Insulation Resistance @500 V DC (1min) MΩ.km 1000 1000
Maximum Conductor Capacitance @800Hz (AC) nF/km 45 45
Maximum Capacitance Unbalance @800Hz
K1 (100% / 50% all values) pF/km 650/150 650/150
K9-12 neighboured quads pF/km 500/150 500/150
K9-12 over-neighboured quads pF/km 150 150
ea1/2 pF/km 1300 1300
Miniumum Far-end Crosstalk Attenuation @90KHz
100% / 80% all values dB/km 58/62 33/45
Maximum Attenuation @90KHz dB/km 3.3 2.6
Dielectric Strength, conductor to conductor (DC voltage 1min) V 3535 3535
Surveillance Conductors
Loop resistance, maximum Ω/km 190 190
Insulation resistance
- dry cable core, minimum MΩ.km 1000 1000
- wet cable core, maximum KΩ.km 30 30
Operating Voltage AC/DC V 420/600 420/600
Test Voltage 50 Hz 1 min
Core to Core Veff 2500 2500
Core to Screen Veff 2500 2500

Mechanical and Thermal Properties

Minimum Bending Radius: 10×OD

Temperature Range: -40℃ to +60℃ (during operation);

                                 -10℃ +60℃ (during installation)

Dimensions And Weight

Cable Code Number of
Quads
Nominal Sheath Thickness
mm
Nominal Overall
Diameter
mm
Nominal
Weight
kg/km
Inner Outer
0.9mm Conductor, 1.8mm Insulated Wire
RS109y-2Y(L)2YB2Y-1Q0.9-S(H45) 1 1.3 1.2 12.0 170
RS109y-2Y(L)2YB2Y-3Q0.9-S(H45) 3 1.3 1.2 17.0 310
RS109y-2Y(L)2YB2Y-5Q0.9-S(H45) 5 1.3 1.2 19.0 410
RS109y-2Y(L)2YB2Y-7Q0.9-S(H45) 7 1.3 1.2 21.0 500
RS109y-2Y(L)2YB2Y-10Q0.9-S(H45) 10 1.3 1.2 24.0 640
RS109y-2Y(L)2YB2Y-14Q0.9-S(H45) 14 1.3 1.2 27.0 800
1.4mm Conductor, 2.8mm Insulated Wire
RS109y-2Y(L)2YB2Y-1Q1.4-S(H45) 1 1.3 1.2 14.0 240
RS109y-2Y(L)2YB2Y-3Q1.4-S(H45) 3 1.3 1.2 21.0 490
RS109y-2Y(L)2YB2Y-5Q1.4-S(H45) 5 1.3 1.2 24.0 710
RS109y-2Y(L)2YB2Y-7Q1.4-S(H45) 7 1.3 1.2 26.0 880
RS109y-2Y(L)2YB2Y-10Q1.4-S(H45) 10 1.3 1.2 33.0 1190
RS109y-2Y(L)2YB2Y-14Q1.4-S(H45) 14 1.3 1.2 36.5 1550