| Mining Cable | |||
| Type W | Type G | Type G-GC | more |
Mining Cable
NTMCWOEU Flexible Medium-Voltage Single Core Cable
Applications
NTMCWOEU Flexible Medium-Voltage Single Core Cables are used for connection in switch-gear and for
connection of mobile transformer substations to the overhead line.
Standards
VDE 0250 Part 813
Construction

Conductors: Flexible stranded tinned copper conductor, class 5 according to DIN VDE 0295.
Inner Conductor Layer: Special conductive rubber.
Insulation: EPR type 3GI3.
Outer Conductor Layer:Special conductive rubber.
Screen: Spiral of tinned copper wires.
Outer Sheath: PCP type 5GM3.
Dimensions and Weight
6/10kV
| Number of Cores×Nominal Cross Section | Insulation Thickness | Thickness of Outer Sheath | Nominal Overall Diameter | Nominal Weight |
|---|---|---|---|---|
| No.×mm² | mm | mm | mm | kg/km |
| 1×16/16 | 3.4 | 2.2 | 22.0 | 760 |
| 1×25/16 | 3.4 | 2.2 | 23.5 | 910 |
| 1×35/16 | 3.4 | 2.2 | 24.5 | 1040 |
| 1×50/16 | 3.4 | 2.2 | 27.0 | 1260 |
| 1×70/16 | 3.4 | 2.5 | 28.5 | 1530 |
| 1×95/16 | 3.4 | 2.5 | 30.5 | 1770 |
| 1×120/16 | 3.4 | 2.5 | 33.5 | 2180 |
| 1×150/25 | 3.4 | 3.0 | 35.0 | 2550 |
| 1×185/25 | 3.4 | 3.0 | 37.0 | 2900 |
| 1×240/25 | 3.4 | 3.5 | 41.0 | 3590 |
| 1×300/25 | 3.4 | 3.5 | 43.0 | 4280 |
| 1×400/35 | 3.4 | 4.0 | 46.0 | 5120 |
| 1×500/35 | 3.4 | 4.0 | 49.0 | 5950 |
| 1×630/35 | 3.4 | 4.0 | 53.5 | 7860 |
12/20kV
| Number of Cores×Nominal Cross Section | Insulation Thickness | Thickness of Outer Sheath | Nominal Overall Diameter | Nominal Weight |
|---|---|---|---|---|
| No.×mm² | mm | mm | mm | kg/km |
| 1×25/16 | 5.5 | 2.5 | 28.0 | 1180 |
| 1×35/16 | 5.5 | 2.5 | 29.5 | 1320 |
| 1×50/16 | 5.5 | 2.5 | 31.5 | 1560 |
| 1×70/16 | 5.5 | 3.0 | 34.0 | 1920 |
| 1×95/16 | 5.5 | 3.0 | 36.0 | 2190 |
| 1×120/16 | 5.5 | 3.0 | 38.0 | 2460 |
| 1×150/25 | 5.5 | 3.5 | 40.0 | 2990 |
| 1×185/25 | 5.5 | 3.5 | 42.0 | 3350 |
| 1×240/25 | 5.5 | 3.5 | 45.0 | 3990 |
| 1×300/25 | 5.5 | 3.5 | 48.0 | 4760 |
| 1×400/35 | 5.5 | 4.0 | 52.0 | 6100 |
| 1×500/35 | 5.5 | 4.0 | 56.0 | 7010 |
| 1×630/35 | 5.5 | 4.0 | 60.0 | 8180 |
14/25kV
| Number of Cores×Nominal Cross Section | Insulation Thickness | Thickness of Outer Sheath | Nominal Overall Diameter | Nominal Weight |
|---|---|---|---|---|
| No.×mm² | mm | mm | mm | kg/km |
| 1×25/16 | 6.8 | 3.0 | 30.5 | 1300 |
| 1×300/25 | 6.8 | 4.0 | 49.0 | 4900 |
18/30kV
| Number of Cores×Nominal Cross Section | Insulation Thickness | Thickness of Outer Sheath | Nominal Overall Diameter | Nominal Weight |
|---|---|---|---|---|
| No.×mm² | mm | mm | mm | kg/km |
| 1×50/16 | 8.0 | 3.0 | 35.0 | 1870 |
20/35 kV
| Number of Cores×Nominal Cross Section | Insulation Thickness | Thickness of Outer Sheath | Nominal Overall Diameter | Nominal Weight |
|---|---|---|---|---|
| No.×mm² | mm | mm | mm | kg/km |
| 1×95/16 | 9.5 | 3.5 | 44.0 | 2900 |
| 1×150/25 | 9.5 | 3.5 | 46.3 | 3600 |
| 1×240/25 | 9.5 | 4.0 | 51.7 | 5000 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information