| Marine Cables | |||
| MariTox Marine Flame Retardant Medium Voltage Cables | MariTox Marine Flame Retardant Power & Control Cables | MariFlex Marine Fire Resistant Power & Control Cables | other |
Marine Cable
P34 BFOU-HCF 0.6/1 kV
Applications :
- P34 BFOU-HCF 0.6/1 kV Marine cables are fire resistant, flame retardant, low smoke and halogen free, used for
- emergency control, power and lighting systems that need to be operational during a 1100℃ hydrocarbon fire.
Standards :
IEC 60092-353
IEC 60092-360
IEC 60332-1
IEC 60332-3-22
IEC 60754-1,2
IEC 61034-1,2
NEK 606


Construction :
Conductors : Tinned annealed stranded compacted copper to IEC 60228 class 2.
Insulation : Mica tape + Halogen free EPR/XLPE.
Bedding : Halogen free compound.
Armour : Tinned copper wire braid.
Outer Sheath1 : Halogen free thermosetting compound, SHF2.
HC-fire protection : Extruded thermoplastic fire protection compound.
Taping : Lapped glass fibre tape.
Outer Sheath2 : Flame retardant halogen-free thermoplastic compound, SHF1, coloured black.
Electrical Characteristics :
-
Nominal Cross Section Area mm² 1.5 2.5 4 6 16 35 Nominal Conductor Diameter mm 1.6 2.1 2.6 3.2 5.1 7.4 Maximum DC Resistant@20℃ Ω/km 12.2 7.56 4.7 3.11 1.16 0.529 Continuous Current Rating@45℃1 Core A 23 30 40 52 96 157 Continuous Current Rating@45℃2 Core A 20 26 34 44 82 133 Continuous Current Rating@45℃3&4 Core A 16 21 28 36 67 110 Short Circuit Current 1s A 210 360 570 860 2290 5010 Operating Voltage KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
-
Nominal Cross Section Area mm² 50 70 95 120 150 185 240 300 Nominal Conductor Diameter mm 8.7 10.3 12.2 13.8 15.1 17.0 19.6 21.9 Maximum DC Resistant@20℃ Ω/km 0.391 0.27 0.195 0.154 0.126 0.1 0.0762 0.0607 Continuous Current Rating@45℃1 Core A 196 242 293 339 389 444 522 601 Continuous Current Rating@45℃2 Core A 167 206 249 288 331 444 444 511 Continuous Current Rating@45℃3&4 Core A 137 169 205 237 272 311 365 421 Short Circuit Current 1s A 7150 10020 13590 17170 21460 26470 34340 42930 Operating Voltage KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 - Note: For more than 4-cores, the current ratings may be calculated from the following formula (IN=I1/ ³√ N ), I1= Current rating for 1-core, N = Number of cores.
Ambient Temperature Correction Factors :
-
Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80 Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Mechanical and Thermal Properties :
Bending Radius :20×OD (during installation); 12×OD (fixed installed).
Temperature Range : -20℃ ~ +90℃.
Dimensions and Weight :
| Construction No. of cores×Cross section mm² |
Nominal Insulation Thickness mm |
Nominal Diameter Over Bedding mm |
Nominal Diameter Over Sheath1 mm |
Nominal Overall Diameter mm |
Nominal Weight kg/km |
|---|---|---|---|---|---|
| 1×50 | 1.4 | 15.0 | 18.5 | 45.5 | 2900 |
| 1×70 | 1.4 | 16.5 | 20.5 | 47.5 | 3300 |
| 1×95 | 1.6 | 18.5 | 23.0 | 50.5 | 3800 |
| 1×120 | 1.6 | 20.5 | 25.0 | 52.5 | 4260 |
| 1×150 | 1.8 | 23.0 | 27.0 | 54.5 | 4750 |
| 1×185 | 2.0 | 25.0 | 29.5 | 57.5 | 5380 |
| 1×240 | 2.2 | 28.0 | 32.5 | 66.0 | 7050 |
| 1×300 | 2.4 | 30.5 | 35.5 | 68.0 | 8000 |
| 2×1.5 | 1.0 | 10.0 | 13.0 | 40.5 | 1890 |
| 2×2.5 | 1.0 | 11.0 | 14.5 | 42.0 | 2080 |
| 3×1.5 | 1.0 | 10.5 | 14.0 | 42.0 | 2140 |
| 3×2.5 | 1.0 | 11.5 | 15.0 | 42.5 | 2200 |
| 3×4 | 1.0 | 13.0 | 16.5 | 43.0 | 2400 |
| 3×6 | 1.0 | 14.0 | 18.0 | 45.0 | 2600 |
| 3×16 | 1.0 | 18.5 | 23.0 | 50.0 | 3500 |
| 3×35 | 1.2 | 25.0 | 29.5 | 57.5 | 4840 |
| 3×70 | 1.4 | 33.0 | 39.0 | 72.0 | 8150 |
| 3×120 | 1.6 | 41.0 | 48.0 | 81.5 | 11300 |
| 3×150 | 1.8 | 46.0 | 54.5 | 88.5 | 13300 |
| 4×2.5 | 1.0 | 12.5 | 16.5 | 44.0 | 2300 |
| 4×6 | 1.0 | 15.5 | 19.5 | 47.5 | 2870 |
| 4×16 | 1.0 | 20.5 | 25.0 | 53.5 | 3830 |
| 7×1.5 | 1.0 | 14.0 | 17.5 | 44.5 | 2550 |
| 12×1.5 | 1.0 | 18.5 | 22.5 | 50.0 | 3140 |
| 27×1.5 | 1.0 | 26.5 | 31.0 | 64.5 | 5070 |
| 7×2.5 | 1.0 | 15.0 | 19.0 | 46.0 | 2760 |
| 12×2.5 | 1.0 | 20.5 | 24.5 | 52.0 | 3500 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information