P15 UX 0.6/1kV
Applications :
- P15 UX 0.6/1kV are flame retardant, low smoke and halogen free, used for earthing and bonding services.
Standards :
IEC 60092-353
IEC 60092-360
IEC 60332-1
IEC 60332-3-22
IEC 60754-1,2
IEC 61034-1,2
NEK 606


Construction :
Conductors : Tinned annealed stranded copper to IEC 60228 class 2 or class 5.
Insulation : Halogen free thermosetting compound, SHF2. When used as protective earth (PE) wire, the cables
coloured yellow/green. When used as single wire, the cables coloured off-white, black, red or blue.
Electrical Characteristics :
-
Nominal Cross Section Area mm² 10 16 25 35 50 70 Nominal Conductor Diameter mm 4 5.1 6.5 7.4 8.7 10.3 Maximum DC Resistant@20℃ Ω/km 1.84 1.16 0.734 0.529 0.391 0.27 Continuous Current Rating@45℃1 Core A 72 96 127 157 196 242 Short Circuit Current 1s A 1430 2290 3580 5010 7150 10020 Operating Voltage KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
-
Nominal Cross Section Area mm² 95 120 150 185 240 300 Nominal Conductor Diameter mm 12.2 13.8 15.1 17.0 19.6 21.9 Maximum DC Resistant@20℃ Ω/km 0.195 0.154 0.126 0.1 0.0762 0.0607 Continuous Current Rating@45℃1 Core A 293 339 389 444 522 601 Short Circuit Current 1s A 13590 17170 21460 26470 34340 42930 Operating Voltage KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Mechanical and Thermal Properties :
- Bending Radius : 8×OD (during installation); 6×OD (fixed installed).
- Temperature Range : -20℃ ~ +90℃.
Dimensions and Weight :
| Construction No. of cores×Cross section (mm²) |
Nominal Insulation Thickness mm |
Nominal Overall Diameter mm |
Nominal Weight kg/km |
|---|---|---|---|
| 1×10 | 1.0 | 6.6 | 125 |
| 1×16 | 1.0 | 7.7 | 185 |
| 1×25 | 1.2 | 9.5 | 290 |
| 1×35 | 1.2 | 10.4 | 380 |
| 1×50 | 1.4 | 12.1 | 510 |
| 1×70 | 1.4 | 13.6 | 700 |
| 1×95 | 1.6 | 15.5 | 950 |
| 1×120 | 1.6 | 17.5 | 1205 |
| 1×150 | 1.8 | 19.4 | 1470 |
| 1×185 | 2.0 | 21.7 | 1875 |
| 1×240 | 2.2 | 24.7 | 2420 |
| 1×300 | 2.4 | 27.2 | 3060 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information