Firetox Flame Retardant Cables 

Firetox Flame Retardant Cables

450/750V XLPE Insulated, LSZH Sheathed Power Cables (2-4cores)

FTX200 07RZ1-R (CU/XLPE/LSZH 450/750V Class 2)

Application

450/750V XLPE Insulated, LSZH Sheathed Power Cables (2-4cores) is mainly used in power stations, mass

transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise

buildings.

Standards

Basic design to BS 7211; IEC 60502-1

450/750V XLPE Insulated, LSZH Sheathed Power Cables (2-4cores)

Fire Performance

Flame Retardance

(Single Vertical

Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE

0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-

1*; DIN VDE 0482-265-2-1*

Reduced Fire

Propagation

(Vertically-mounted

bundled wires

& cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-

004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-

4

Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas

Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*

minimum Smoke

Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-

1&2*; BS 7622-1&2*

No Toxic gases NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.

Voltage Rating

450/750V

Cable Construction

Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.

Insulation: Extruded cross-linked XLPE compound.

Filler, binder (if any): PP, PET

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound

type SW2-SW4 as per BS 7655-2.6 can be offered.)

Colour Code

Insulation colour as per bs7671

  with earth conductor without earth conductor
2Cores - Brown,Blue
3Cores Yellow/Green,Brown,Blue Brown,Gray,Black
4Cores Yellow/Green,Brown,Gray,Black Brown,Gray,Black,Blue
5Cores Yellow/Green,Brown,Gray,Black,Blue Brown,Gray,Black,Blue,Black
above 5 Cores Yellow/Green,Black Numbered Black Numbered

sheath colour: Black

Physical And Thermal Properties

Temperature range during operation: Max.90°C for XLPE

250°C in short-circuit for 5s max.

Minimum bending radius: 6 x Overall Diameter

Construction Parameters

Conductor FTX200 05ROZ1-R
No. Of Core X
Cross
Section
No./ Nominal
Diameter
Of
Strands
Nominal Overall
Diameter
Conductor
Nominal Insulation
Thickness
Nominal Sheath
Thickness
Nominal Overall
Diameter
Max.Dc Resistance
Of
Conductor
@20°C
Approx.
Weight
Noxmm2 No./mm mm mm mm mm Ω/km kg/km
2x1.0 7/0.44 1.32 0.7 1.2 8.5 18.1 101
2x1.5 7/0.53 1.59 0.7 1.2 9.1 12.1 120
2x2.5 7/0.67 2.01 0.7 1.2 10.0 7.41 154
2x4.0 7/0.85 2.55 0.7 1.3 11.1 4.61 205
3x1.0 7/0.44 1.32 0.7 1.2 9.0 18.1 118
3x1.5 7/0.53 1.59 0.7 1.2 9.6 12.1 142
3x2.5 7/0,67 2.01 0.7 1.2 10.6 7.41 185
3x4.0 7/0.85 2.55 0.7 1.3 11.8 4.61 251
4x1.0 7/0.44 1.32 0.7 1.2 9.8 18.1 141
4x1.5 7/0.53 1.59 0.7 1.2 10.5 12.1 171
4x2.5 7/0.67 2.01 0.7 1.3 11.6 7.41 226
4x4.0 7/0.85 2.55 0.7 1.3 13.0 4.61 309

Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information

Electrical PROPERTIES

Conductor Operating Temperature : 90°C

Ambient Temperature : 30°C

Current-Carrying Capacities (Amp)

Conductor cross- sectional area Reference method
4 (enclosed in conduit in thermally insulating wall etc)
Reference
method 3 (enclosed in conduit on
a wall or in
trunking etc)
Reference method
1 (clipped direct)
Reference method 11 (on a perforated cable tray, horizontal or vertical) Reference method 12 (free air)
Horizontal flat spaced Vertical flat spaced Trefoil
  2 cables, single- phase a.c. or d.c. 3 or 4 cables,
3-phase a.c.
2 cables, single- phase a.c. or d.c 3 or 4 cables,
3-phase a.c.
2 cables, single- phase a.c. or d.c. flat and touching 3 or 4 cables,
3-phase a.c. flat and touching or trefoil
2 cables, single- phase a.c. or d.c. or flat and touching 3 or 4 cables,
3-phase a.c. flat and touching or trefoil
2 cables,
single- phase a.c. or d.c.
or 3 c ables three
phase
2 cables,
single- phase a.c. or d.c.
or 3 cables three
phase
3 cables, trefoil
3- phase a.c.
1 2 3 4 5 6 7 8 9 10 11 12
mm2 A A A A A A A A A A A
1.0 13 - - - 15 - - - - - -
1.5 18 17 22 19 25 23 - - - - -
2.5 24 23 30 26 34 31 - - - - -
4 33 30 40 35 46 41 - - - - -

Voltage Drop (Per Amp Per Meter)

Nominal
Cross
Section
Area
2 cables
d.c.
2 cables, single-phase a.c. 3 or 4 cables, 3-phase a.c.
Ref. Methods 3 and 4 (enclosed
in conduit etc,
in or on a wall)
Ref. Methods 1 and 11 (clipped
direct or on trays
touching)
Ref. Methods 3 and 4 (enclosed
in conduit etc,
in or on a wall)
Ref. Methods 1, 11 and 12 (in
trefoil)
Ref. Methods 1 and
11(Flat and touching)
1 2 3 4 5 6 7
mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
1.0 46 46 - - - -
1.5 31 31 27 27 27 27
2.5 19 19 16 16 16 16
4 33 12 10 10 10 10