| Firetox Flame Retardant Cables | |||
Firetox Flame Retardant Cables
      
      600/1000V LSZH Insulated, Non-sheathed Power Cables to BS EN 50525-3-41 (Single Core)
 FTX100 1Z-R (CU/LSZH 600/1000V Class 2)
  
APPLICATION
600/1000V LSZH Insulated, Non-sheathed Power Cables to BS EN 50525-3-41 (Single Core) are mainly
used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels,
hospitals and high-rise buildings.
STANDARDS
![]()
Basic design adapted to BS EN 50525-3-41

FIRE PERFORMANCE
| Flame Retardance (Single vertical wire or cable test) | IEC 60332-1-2; EN 60332-1-2  | 
  
|---|---|
Halogen Free  | 
    IEC 60754-1; EN 50267-2-1  | 
  
No Corrosive Gas Emission  | 
    IEC 60754-2; EN 50267-2-2  | 
  
Minimum Smoke Emission  | 
    IEC 61034-2; EN 61034-2  | 
  
CPR Compliance  | 
    Eca  | 
  
VOLTAGE RATING
600/1000V
CABLE CONSTRUCTION
Conductor : Annealed copper conductor, stranded according to BS EN 60228 class 2.
Insulation : Crosslinked polyolefin material type EI 5 according to EN 50363-5.
Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties
can be offered as option.
COLOUR CODE
Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow. Bi-colours of any
combination of the above mono-colours are permitted.
PHYSICAL AND THERMAL PROPERTIES
Maximum temperature range during operation : 90°C
Maximum short circuit temperature (5 Seconds) : 250°C
Minimum bending radius :
OD<8mm : 4 × Overall Diameter
8mm≤OD≤12mm : 5 × Overall Diameter
OD>12mm : 6 × Overall Diameter
CONSTRUCTION PARAMETERS
| Conductor | FTX100 1Z-R  | 
  |||
|---|---|---|---|---|
No. of Cores × Cross-sectional Area  | 
    Conductor Class  | 
    Nominal Insulation Thickness  | 
    Nominal Overall Diameter  | 
    Approx. Weight  | 
  
No.×mm²  | 
    
  | 
    mm  | 
    mm  | 
    kg/km  | 
  
1x1.5  | 
    2  | 
    0.7  | 
    3.1  | 
    23  | 
  
1x2.5  | 
    2  | 
    0.8  | 
    3.7  | 
    35  | 
  
1x4.0  | 
    2  | 
    0.8  | 
    4.3  | 
    52  | 
  
1x6.0  | 
    2  | 
    0.8  | 
    4.8  | 
    73  | 
  
1x10  | 
    2  | 
    1.0  | 
    6.2  | 
    120  | 
  
1x16  | 
    2  | 
    1.0  | 
    7.2  | 
    180  | 
  
1x25  | 
    2  | 
    1.2  | 
    9.0  | 
    285  | 
  
1x35  | 
    2  | 
    1.2  | 
    10.2  | 
    375  | 
  
1x50  | 
    2  | 
    1.4  | 
    12.0  | 
    510  | 
  
1x70  | 
    2  | 
    1.4  | 
    14.0  | 
    720  | 
  
1x95  | 
    2  | 
    1.6  | 
    16.0  | 
    995  | 
  
1x120  | 
    2  | 
    1.6  | 
    18.0  | 
    1230  | 
  
1x150  | 
    2  | 
    1.8  | 
    20.0  | 
    1520  | 
  
1x185  | 
    2  | 
    2.0  | 
    22.0  | 
    1900  | 
  
1x240  | 
    2  | 
    2.2  | 
    25.0  | 
    2480  | 
  
1x300  | 
    2  | 
    2.4  | 
    28.0  | 
    3100  | 
  
1x400  | 
    2  | 
    2.6  | 
    31.5  | 
    3950  | 
  
1x500  | 
    2  | 
    2.8  | 
    35.0  | 
    4950  | 
  
1x630  | 
    2  | 
    2.8  | 
    39.0  | 
    6360  | 
  
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information
ELECTRICAL PROPERTIES
Conductor operating temperature : 90°C
Ambient temperature : 30°C
Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4E1A
Conductor cross-sectional area  | 
    Ref. Method A (enclosed in conduit in thermally insulating wall etc.)  | 
    Ref. Method B (enclosed in conduit on a wall or in trunking etc.)  | 
    Ref. Method C (clipped direct)  | 
    Ref. Method F (in free air or on a perforated cable tray, horizontal or vertical etc.) Touching  | 
    Ref. Method G (in free air) spaced by one cable diameter  | 
  ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
2 cables, single-phase a.c. or d.c.  | 
    3 or 4 cables, three-phase a.c.  | 
    2 cables, single-phase a.c. or d.c  | 
    3 or 4 cables, three-phase a.c.  | 
    2 cables, single-phase a.c. or d.c. flat and touching  | 
    3 or 4 cables, three-phase a.c. flat and touching or trefoil  | 
    2 cables, single-phase a.c. or d.c. flat  | 
    3 cables, three-phase a.c. flat  | 
    3 cables, three-phase a.c. trefoil  | 
    2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat  | 
  ||
Horizontal  | 
    Vertical  | 
  ||||||||||
1  | 
    2  | 
    3  | 
    4  | 
    5  | 
    6  | 
    7  | 
    8  | 
    9  | 
    10  | 
    11  | 
    12  | 
  
mm²  | 
    A  | 
    A  | 
    A  | 
    A  | 
    A  | 
    A  | 
    A  | 
    A  | 
    A  | 
    A  | 
    A  | 
  
1.5  | 
    19  | 
    17  | 
    23  | 
    20  | 
    25  | 
    23  | 
    -  | 
    -  | 
    -  | 
    -  | 
    -  | 
  
2.5  | 
    26  | 
    23  | 
    31  | 
    28  | 
    34  | 
    31  | 
    -  | 
    -  | 
    -  | 
    -  | 
    -  | 
  
4.0  | 
    35  | 
    31  | 
    42  | 
    37  | 
    46  | 
    41  | 
    -  | 
    -  | 
    -  | 
    -  | 
    -  | 
  
6.0  | 
    45  | 
    40  | 
    54  | 
    48  | 
    59  | 
    54  | 
    -  | 
    -  | 
    -  | 
    -  | 
    -  | 
  
10  | 
    61  | 
    54  | 
    75  | 
    66  | 
    81  | 
    74  | 
    -  | 
    -  | 
    -  | 
    -  | 
    -  | 
  
16  | 
    81  | 
    73  | 
    100  | 
    88  | 
    109  | 
    99  | 
    -  | 
    -  | 
    -  | 
    -  | 
    -  | 
  
25  | 
    106  | 
    95  | 
    133  | 
    117  | 
    143  | 
    130  | 
    161  | 
    141  | 
    135  | 
    182  | 
    161  | 
  
35  | 
    131  | 
    117  | 
    164  | 
    144  | 
    176  | 
    161  | 
    200  | 
    176  | 
    169  | 
    226  | 
    201  | 
  
50  | 
    158  | 
    141  | 
    198  | 
    175  | 
    228  | 
    209  | 
    242  | 
    216  | 
    207  | 
    275  | 
    246  | 
  
70  | 
    200  | 
    179  | 
    253  | 
    222  | 
    293  | 
    268  | 
    310  | 
    279  | 
    268  | 
    353  | 
    318  | 
  
95  | 
    241  | 
    216  | 
    306  | 
    269  | 
    355  | 
    326  | 
    377  | 
    342  | 
    328  | 
    430  | 
    389  | 
  
120  | 
    278  | 
    249  | 
    354  | 
    312  | 
    413  | 
    379  | 
    437  | 
    400  | 
    383  | 
    500  | 
    454  | 
  
150  | 
    318  | 
    285  | 
    393  | 
    342  | 
    476  | 
    436  | 
    504  | 
    464  | 
    444  | 
    577  | 
    527  | 
  
185  | 
    362  | 
    324  | 
    449  | 
    384  | 
    545  | 
    500  | 
    575  | 
    533  | 
    510  | 
    661  | 
    605  | 
  
240  | 
    424  | 
    380  | 
    528  | 
    450  | 
    644  | 
    590  | 
    679  | 
    634  | 
    607  | 
    781  | 
    719  | 
  
300  | 
    486  | 
    435  | 
    603  | 
    514  | 
    743  | 
    681  | 
    783  | 
    736  | 
    703  | 
    902  | 
    833  | 
  
400  | 
    -  | 
    -  | 
    683  | 
    584  | 
    868  | 
    793  | 
    940  | 
    868  | 
    823  | 
    1085  | 
    1008  | 
  
500  | 
    -  | 
    -  | 
    783  | 
    666  | 
    990  | 
    904  | 
    1083  | 
    998  | 
    946  | 
    1253  | 
    1169  | 
  
630  | 
    -  | 
    -  | 
    900  | 
    764  | 
    1130  | 
    1033  | 
    1254  | 
    1151  | 
    1088  | 
    1454  | 
    1362  | 
  
Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E1B
Conductor cross-sectional area  | 
    2 cables d.c.  | 
    2 cables, single-phase a.c.  | 
    3 or 4 cables, three-phase a.c.  | 
  |||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Ref. Methods A&B (enclosed in conduit or trunking)  | 
    Ref. Methods C, F&G (clipped direct, on trays or in free air)  | 
    Ref. Methods A&B (enclosed in conduit or trunking)  | 
    Ref. Methods C, F&G (clipped direct, on trays or in free air)  | 
  |||||||||||||||||||
cables touching  | 
    cables spaced*  | 
    Cables touching, Trefoil  | 
    Cables touching, Flat  | 
    Cables spaced*, Flat  | 
  ||||||||||||||||||
1  | 
    2  | 
    3  | 
    4  | 
    5  | 
    6  | 
    7  | 
    8  | 
    9  | 
  ||||||||||||||
mm²  | 
    mV/A/m  | 
    mV/A/m  | 
    mV/A/m  | 
    mV/A/m  | 
    mV/A/m  | 
    mV/A/m  | 
    mV/A/m  | 
  |||||||||||||||
1.5  | 
    31  | 
    31  | 
    31  | 
    31  | 
    27  | 
    27  | 
    27  | 
    27  | 
  ||||||||||||||
2.5  | 
    19  | 
    19  | 
    19  | 
    19  | 
    16  | 
    16  | 
    16  | 
    16  | 
  ||||||||||||||
4.0  | 
    12  | 
    12  | 
    12  | 
    12  | 
    10  | 
    10  | 
    10  | 
    10  | 
  ||||||||||||||
6.0  | 
    7.9  | 
    7.9  | 
    7.9  | 
    7.9  | 
    6.8  | 
    6.8  | 
    6.8  | 
    6.8  | 
  ||||||||||||||
10  | 
    4.7  | 
    4.7  | 
    4.7  | 
    4.7  | 
    4.0  | 
    4.0  | 
    4.0  | 
    4.0  | 
  ||||||||||||||
16  | 
    2.9  | 
    2.9  | 
    2.9  | 
    2.9  | 
    2.5  | 
    2.5  | 
    2.5  | 
    2.5  | 
  ||||||||||||||
  | 
    
  | 
    r  | 
    x  | 
    z  | 
    r  | 
    x  | 
    z  | 
    r  | 
    x  | 
    z  | 
    r  | 
    x  | 
    z  | 
    r  | 
    x  | 
    z  | 
    r  | 
    x  | 
    z  | 
    r  | 
    x  | 
    z  | 
  
25  | 
    1.85  | 
    1.85  | 
    0.31  | 
    1.90  | 
    1.85  | 
    0.190  | 
    1.85  | 
    1.85  | 
    0.28  | 
    1.85  | 
    1.60  | 
    0.27  | 
    1.65  | 
    1.60  | 
    0.165  | 
    1.60  | 
    1.60  | 
    0.190  | 
    1.60  | 
    1.60  | 
    0.27  | 
    1.65  | 
  
35  | 
    1.35  | 
    1.35  | 
    0.29  | 
    1.35  | 
    1.35  | 
    0.180  | 
    1.35  | 
    1.35  | 
    0.27  | 
    1.35  | 
    1.15  | 
    0.25  | 
    1.15  | 
    1.15  | 
    0.155  | 
    1.15  | 
    1.15  | 
    0.180  | 
    1.15  | 
    1.15  | 
    0.26  | 
    1.20  | 
  
50  | 
    0.99  | 
    1.00  | 
    0.29  | 
    1.05  | 
    0.99  | 
    0.180  | 
    1.00  | 
    0.99  | 
    0.27  | 
    1.00  | 
    0.87  | 
    0.25  | 
    0.90  | 
    0.86  | 
    0.155  | 
    0.87  | 
    0.86  | 
    0.180  | 
    0.87  | 
    0.86  | 
    0.26  | 
    0.89  | 
  
70  | 
    0.68  | 
    0.70  | 
    0.28  | 
    0.75  | 
    0.68  | 
    0.175  | 
    0.71  | 
    0.68  | 
    0.26  | 
    0.73  | 
    0.60  | 
    0.24  | 
    0.65  | 
    0.59  | 
    0.150  | 
    0.61  | 
    0.59  | 
    0.175  | 
    0.62  | 
    0.59  | 
    0.25  | 
    0.65  | 
  
95  | 
    0.49  | 
    0.51  | 
    0.27  | 
    0.58  | 
    0.49  | 
    0.170  | 
    0.52  | 
    0.49  | 
    0.26  | 
    0.56  | 
    0.44  | 
    0.23  | 
    0.50  | 
    0.43  | 
    0.145  | 
    0.45  | 
    0.43  | 
    0.170  | 
    0.46  | 
    0.43  | 
    0.25  | 
    0.49  | 
  
120  | 
    0.39  | 
    0.41  | 
    0.26  | 
    0.48  | 
    0.39  | 
    0.165  | 
    0.43  | 
    0.39  | 
    0.25  | 
    0.47  | 
    0.35  | 
    0.23  | 
    0.42  | 
    0.34  | 
    0.140  | 
    0.37  | 
    0.34  | 
    0.165  | 
    0.38  | 
    0.34  | 
    0.24  | 
    0.42  | 
  
150  | 
    0.32  | 
    0.33  | 
    0.26  | 
    0.43  | 
    0.32  | 
    0.165  | 
    0.36  | 
    0.32  | 
    0.25  | 
    0.41  | 
    0.29  | 
    0.23  | 
    0.37  | 
    0.28  | 
    0.140  | 
    0.31  | 
    0.28  | 
    0.165  | 
    0.32  | 
    0.28  | 
    0.24  | 
    0.37  | 
  
185  | 
    0.25  | 
    0.27  | 
    0.26  | 
    0.37  | 
    0.26  | 
    0.165  | 
    0.30  | 
    0.25  | 
    0.25  | 
    0.36  | 
    0.23  | 
    0.23  | 
    0.32  | 
    0.22  | 
    0.140  | 
    0.26  | 
    0.22  | 
    0.165  | 
    0.28  | 
    0.22  | 
    0.24  | 
    0.33  | 
  
240  | 
    0.190  | 
    0.21  | 
    0.26  | 
    0.33  | 
    0.20  | 
    0.160  | 
    0.25  | 
    0.195  | 
    0.25  | 
    0.31  | 
    0.185  | 
    0.22  | 
    0.29  | 
    0.170  | 
    0.140  | 
    0.22  | 
    0.170  | 
    0.165  | 
    0.24  | 
    0.170  | 
    0.24  | 
    0.29  | 
  
300  | 
    0.155  | 
    0.175  | 
    0.25  | 
    0.31  | 
    0.160  | 
    0.160  | 
    0.22  | 
    0.155  | 
    0.25  | 
    0.29  | 
    0.150  | 
    0.22  | 
    0.27  | 
    0.140  | 
    0.140  | 
    0.195  | 
    0.135  | 
    0.160  | 
    0.21  | 
    0.135  | 
    0.24  | 
    0.27  | 
  
400  | 
    0.120  | 
    0.140  | 
    0.25  | 
    0.29  | 
    0.130  | 
    0.155  | 
    0.20  | 
    0.125  | 
    0.24  | 
    0.27  | 
    0.125  | 
    0.22  | 
    0.25  | 
    0.110  | 
    0.135  | 
    0.175  | 
    0.110  | 
    0.160  | 
    0.195  | 
    0.110  | 
    0.24  | 
    0.26  | 
  
500  | 
    0.093  | 
    0.120  | 
    0.25  | 
    0.28  | 
    0.105  | 
    0.155  | 
    0.185  | 
    0.098  | 
    0.24  | 
    0.26  | 
    0.100  | 
    0.22  | 
    0.24  | 
    0.090  | 
    0.135  | 
    0.160  | 
    0.088  | 
    0.160  | 
    0.180  | 
    0.085  | 
    0.24  | 
    0.25  | 
  
630  | 
    0.072  | 
    0.100  | 
    0.25  | 
    0.27  | 
    0.086  | 
    0.155  | 
    0.175  | 
    0.078  | 
    0.24  | 
    0.25  | 
    0.088  | 
    0.21  | 
    0.23  | 
    0.074  | 
    0.135  | 
    0.150  | 
    0.071  | 
    0.160  | 
    0.170  | 
    0.068  | 
    0.23  | 
    0.24  | 
  
Note : *Spacings larger than one cable  diameter will result in a large voltage drop.
  r = conductor resistance at operating  temperature
  x = reactance
  z = impedance