FIREGUARD Flame Retardant Cables

Fire retardant cable(Fireguard)

600/1000V PVC Insulated, PVC Sheathed, Armoured Power Cables to IEC 60502 (2-5 Cores & Multicore)

FGD400 1VVMV-R (CU/PVC/PVC/SWA/PVC 600/1000V Class 2)

 

 

Application

600/1000V PVC Insulated, PVC Sheathed, Armoured Power Cables to IEC 60502 (2-5 Cores & Multicore)

are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants,

hotels, hospitals, and high-rise buildings.

Cable Construction

Conductor

Annealed copper wire, stranded according to IEC 60228 class 2.

Insulation

PVC/A according to IEC 60502-1.

Inner Covering

Extruded PVC or polymeric compound.

Armouring

Galvanized steel wire

Outer Sheath

Extruded PVC Type ST1/ST2 according to IEC 60502-1.

Outer Sheath Option

UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

Standards

Basic design adapted to IEC 60502-1

FGD400 1VVMV-R (CU/PVC/PVC/SWA/PVC 600/1000V Class 2)

Fire Performance

Flame Retardance (Single Vertical Wire Test)

IEC 60332-1-2

Voltage Rating

600/1000V

Colour Code


Insulation Colour

Two-core: Brown, blue
Three-core: Brown, black, grey
Four-core: Blue, brown, black, grey
Five-core: Green-and-yellow, blue, brown, black, grey
Other colours can be offered upon request.

Sheath Colour

Black, other colours can be offered upon request.

Physical AND THERMAL PROPERTIES


Maximum temperature range during operation (PVC)

70°C

Maximum short circuit temperature (5 Seconds)

160°C(≤300 mm²); 140°C(>300 mm²)

Minimum bending radius

Circular copper conductors

6 x Overall Diameter

Shaped copper conductors

8 x Overall Diameter

Construction Parameters

Conductor

FGD400 1VVMV-R

No. of Cores x Cross Section

Class of Conductor

Nominal Insulation
Thickness

Nominal Inner Covering
Thickness

Armour Wire Diameter

Nominal Sheath Thickness

Nominal Overall
Diameter

Approx. Weight

No.xmm2

 

mm

mm

mm

mm

mm

kg/km

2 Cores

2x2.5

2

0.8

1.0

0.8

1.8

14.0

380

2x4.0

2

1.0

1.0

1.25

1.8

16.7

604

2x6.0

2

1.0

1.0

1.25

1.8

17.7

689

2x10

2

1.0

1.0

1.25

1.8

19.3

841

2x16

2

1.0

1.0

1.25

1.8

21.1

1037

2x25

2

1.2

1.0

1.6

1.8

24.8

1513

2x35

2

1.2

1.0

1.6

1.8

27.0

1843

2x50

2

1.4

1.0

1.6

1.9

30.7

2356

2x70

2

1.4

1.0

2.0

2.1

34.5

3179

2x95

2

1.6

1.2

2.0

2.2

39.2

4042

2x120

2

1.6

1.2

2.0

2.3

42.2

4764

2x150

2

1.8

1.2

2.5

2.5

47.2

6095

2x185

2

2.0

1.4

2.5

2.6

51.6

7207

2x240

2

2.2

1.4

2.5

2.8

57.2

8861

2x300

2

2.4

1.6

2.5

3.0

62.8

10608

2x400

2

2.6

1.6

2.5

3.2

70.3

13385

3 Cores

3x2.5

2

0.8

1.0

0.8

1.8

14.5

432

3x4.0

2

1.0

1.0

1.25

1.8

17.4

689

3x6.0

2

1.0

1.0

1.25

1.8

18.4

800

3x10

2

1.0

1.0

1.25

1.8

20.2

1001

3x16

2

1.0

1.0

1.6

1.8

22.8

1405

3x25

2

1.2

1.0

1.6

1.8

26.0

1860

3x35

2

1.2

1.0

1.6

1.9

28.5

2325

3x50

2

1.4

1.0

2.0

2.0

33.3

3266

3x70

2

1.4

1.2

2.0

2.1

37.0

4108

3x95

2

1.6

1.2

2.0

2.3

41.6

5245

3x120

2

1.6

1.2

2.5

2.4

45.9

6677

3x150

2

1.8

1.4

2.5

2.6

50.4

8016

3x185

2

2.0

1.4

2.5

2.7

54.8

9466

3x240

2

2.2

1.5

2.5

2.9

61.2

11805

3x300

2

2.4

1.6

2.5

3.1

66.8

14181

3x400

2

2.8

1.6

3.15

3.4

76.7

19235

3x500

2

2.8

1.8

3.15

3.7

83.6

23011

3 Cores+1 Earth Conductor

3x10/6

2

1.0

1.0

1.0

1.25

1.8

21.9

1140

3x16/10

2

1.0

1.0

1.0

1.6

1.8

24.2

1633

3x25/16

2

1.2

1.0

1.0

1.6

1.8

27.9

2145

3x35/16

2

1.2

1.0

1.0

1.6

1.9

30.8

2659

3x50/25

2

1.4

1.2

1.0

2.0

2.0

36.4

3739

3x70/35

2

1.4

1.2

1.2

2.0

2.1

40.1

4720

3x95/50

2

1.6

1.4

1.2

2.5

2.3

46.3

6398

3x120/70

2

1.6

1.4

1.4

2.5

2.4

50.3

7746

3x150/70

2

1.8

1.4

1.4

2.5

2.6

55.0

9128

3x185/95

2

2.0

1.6

1.4

2.5

2.7

60.3

10916

3x240/120

2

2.2

1.6

1.6

2.5

2.9

67.0

13713

3x300/150

2

2.4

1.8

1.6

3.15

3.1

74.6

17403

3x400/185

2

2.6

2.0

1.8

3.15

3.4

84.1

20704

3x500/240

2

2.8

2.2

2.0

3.15

3.7

91.8

25817

4 Cores

4x4.0

2

1.0

1.0

1.25

1.8

18.5

792

4x6.0

2

1.0

1.0

1.25

1.8

19.7

931

4x10

2

1.0

1.0

1.25

1.8

22.3

1185

4x16

2

1.0

1.0

1.6

1.8

24.5

1672

4x25

2

1.2

1.0

1.6

1.9

28.2

2260

4x35

2

1.2

1.0

1.6

2.0

31.1

2854

4x50

2

1.4

1.0

2.0

2.1

36.7

4013

4x70

2

1.4

1.2

2.0

2.3

40.4

5104

4x95

2

1.6

1.2

2.5

2.5

46.6

6996

4x120

2

1.6

1.4

2.5

2.6

50.6

8400

4x150

2

1.8

1.4

2.5

2.7

55.3

10008

4x185

2

2.0

1.4

2.5

2.9

60.6

11906

4x240

2

2.2

1.6

2.5

3.1

67.3

14963

4x300

2

2.4

1.6

3.15

3.4

74.9

18944

4x400

2

2.6

1.8

3.15

3.7

84.4

24304

4x500

2

2.8

2.0

3.15

3.9

92.1

29351

Conductor

FGD400 1VVMV-R

No. of Cores x Cross Section

Class of Conductor

Nominal Insulation
Thickness

Nominal Inner Covering
Thickness

Armour Wire Diameter

Nominal Sheath Thickness

Nominal Overall
Diameter

Approx. Weight

No.xmm2

 

mm

mm

mm

mm

mm

kg/km

5 Cores

5x1.5

2

0.8

1.0

1.25

1.8

17.5

587

5x2.5

2

0.8

1.0

1.25

1.8

18.7

681

5x4

2

1

1.0

1.25

1.8

21.3

879

5x6

2

1

1.0

1.6

1.8

23.8

1183

5x10

2

1

1.0

1.6

1.8

26.3

1508

5x16

2

1

1.0

1.6

1.9

29.3

1947

5x25

2

1.2

1.0

2.0

2.1

35.2

2942

5x35

2

1.2

1.2

2.0

2.2

38.9

3659

Multicore

7x1.5

2

0.8

1.0

1.25

1.8

18.5

671

8x1.5

2

0.8

1.0

1.25

1.8

19.4

731

10x1.5

2

0.8

1.0

1.25

1.8

20.7

863

12x1.5

2

0.8

1.0

1.6

1.8

22.9

1064

19x1.5

2

0.8

1.0

1.6

1.8

25.6

1350

27x1.5

2

0.8

1.0

1.6

1.9

29.5

1717

37x1.5

2

0.8

1.0

1.6

2.0

32.5

2089

48x1.5

2

0.8

1.2

2.0

2.1

36.7

2845

7x2.5

2

0.8

1.0

1.25

1.8

19.6

790

8x2.5

2

0.8

1.0

1.25

1.8

21.0

865

10x2.5

2

0.8

1.0

1.6

1.8

24.2

1173

12x2.5

2

0.8

1.0

1.6

1.8

27.9

1265

19x2.5

2

0.8

1.0

1.6

1.8

28.0

1638

27x2.5

2

0.8

1.0

1.6

2.0

32.5

2125

37x2.5

2

0.8

1.2

2.0

2.1

36.9

2922

48x2.5

2

0.8

1.2

2.0

2.3

41.7

3561

Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information

Note: Other conductor sizes & core confi gurations are available upon request.
ELECTRICAL PROPERTIES

Conductor Operating Temperature

70°C

Ambient Temperature

30°C

Current-Carrying Capacities (Amp) according to BS 7671: 2008 table 4D4A


Conductor crosssectional
area

Reference Method C (clipped direct)

Reference Method E (in free air or
on a perforated cable tray, horizontal
or vertical)

Reference Method D (direct in in
groud or in ducting in groud. in or
around buildings)

1 two-core cable,
single-phase a.c.
or d.c.

1 three-or four
core cable,
three-phase a.c.

1 two-core
cable, singlephase
a.c. or
d.c.

1 three-or four
core cable,
three-phase a.c.

1 two-core cable,
single-phase a.c.
or d.c.

1 three-or four
core cable, threephase
a.c.

1

2

3

4

5

6

7

mm2

A

A

A

A

A

A

1.5

21

18

22

19

22

18

2.5

28

25

31

26

29

24

4.0

38

33

41

35

37

30

6.0

49

42

53

45

46

38

10

67

58

72

62

60

50

16

89

77

97

83

78

64

25

118

102

128

110

99

82

35

145

125

157

135

119

98

50

175

151

190

163

140

116

70

222

192

241

207

173

143

95

269

231

291

251

204

169

120

310

267

336

290

231

192

150

356

306

386

332

261

217

185

405

348

439

378

292

243

240

476

409

516

445

336

280

300

547

469

592

510

379

316

400

621

540

683

590

-

-

Voltage Drop (Per Amp Per Meter) according to BS 7671: 2008 table 4D4B


Nominal Cross Section  Area

Two-core cables d.c.

Two-core cable, single-phase a.c.

Three- or four-core cable, three-phase a.c.

1

2

3

4

mm2

mV/A/m

mV/A/m

mV/A/m

1.5

29

29

25

2.5

18

18

15

4.0

11

11

9.5

6.0

7.3

7.3

6.4

10

4.4

4.4

3.8

16

2.8

2.8

2.4

 

 

r

x

z

r

x

z

25

1.75

1.75

0.170

1.75

1.50

0.145

1.50

35

1.25

1.25

0.165

1.25

1.10

0.145

1.10

50

0.93

0.93

0.165

0.94

0.80

0.140

0.81

70

0.63

0.63

0.160

0.65

0.55

0.140

0.57

95

0.46

0.47

0.155

0.50

0.41

0.135

0.43

120

0.36

0.38

0.155

0.41

0.33

0.135

0.35

150

0.29

0.30

0.155

0.34

0.26

0.130

0.29

185

0.23

0.25

0.150

0.29

0.21

0.130

0.25

240

0.180

0.190

0.150

0.24

0.165

0.130

0.21

300

0.145

0.155

0.145

0.21

0.135

0.130

0.185

400

0.105

0.115

0.145

0.185

0.100

0.125

0.160

Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance