Fire Resistant RS485 Databus Cables
Application
Fire Resistant RS485 Databus Cables are designed for RS485 data connections where continued functionality is
required during a fire situation. This cable combines low capacitance insulation with one of the highest levels of
screening to provide high speed, interference free, data transmission where continued functionality is required
during a fire situation.
Standards
Basic design to EIA/TIA 485

Fire Performance
| Circuit Integrity | IEC 60331-23; BS 6387 CWZ; DIN VDE 0472-814(FE180); CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) |
|---|---|
| System circuit integrity | DIN 4102-12, E30 depending on lay system |
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332- 3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2- 4*; DIN VDE 0482-266-2-4 |
| Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
| No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
| Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
| No Toxic gases | NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard..
Cable Construction
Multipair RS 485 Overall Screened Databus Cable
Conductors: tinned copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: mica glass tape wrapped with PE or PE wrapped with silicone rubber insulation.
Cabling Elements: Insulated cores are twisted to form pairs with varying lay length to minimize crosstalk. Two
pair cable had four cores laid in quad formation.
Cabling: Pairs are cabled together in concentric layers.
Overall screen: Aluminum/polyester tape with tinned copper drain wire.
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound
type SW2-SW4 as per BS 7655-2.6 can be offered.)
Multipair RS 485 Overall Double Screened Databus Cable
Conductors: tinned copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: mica glass tape wrapped with PE or PE wrapped with silicone rubber insulation.
Cabling Elements: Insulated cores are twisted to form pairs with varying lay length to minimize crosstalk. Two
pair cable had four cores laid in quad formation.
Cabling: Pairs are cabled together in concentric layers.
Overall screen: Aluminium/polyester tape+copper wire braid.
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound
type SW2-SW4 as per BS 7655-2.6 can be offered.)
Multipair RS 485 Individual & Overall screened Databus Cable
Conductors: tinned copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: mica glass tape wrapped with PE or PE wrapped with silicone rubber insulation.
Cabling Elements: Insulated cores are twisted to form pairs with varying lay length to minimize crosstalk. Two
pair cable had four cores laid in quad formation.
Cabling: Pairs are cabled together in concentric layers.
Individual Screen: Individual aluminium/polyester tape.
Overall Screen: Copper wire braid.
outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound
type SW2-SW4 as per BS 7655-2.6 can be offered.)
Multipair RS 485 Overall Screened Databus Cable
Conductors: tinned copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: mica glass tape wrapped with PE or PE wrapped with silicone rubber insulation.
Cabling Elements: Insulated cores are twisted to form pairs with varying lay length to minimize crosstalk. Two
pair cable had four cores laid in quad formation.
Cabling: Pairs are cabled together in concentric layers.
Overall Screen: Copper wire braid.
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound
type SW2-SW4 as per BS 7655-2.6 can be offered.)
Physical And Thermal Properties
Temperature range during operation (fixed state): -20°C - +90°C
Temperature range during installation (mobile state): -5°C - +60°C
Minimum bending radius: 8 x Overall Diameter
Electrical Properties
Dielectric test:1000 V r.m.s. for 5’ (core-core)
1000 V r.m.s. for 5’ (core-screen)
Impedance:120Ω
Capacitance:45 nF/km conductor to conductor
90 nF/km conductor to shield
Construction Parameters
Multipair RS 485 Overall Screened Databus Cable
RE-m02Y(ST)H-FR / RE-m02YS(ST)H-FR
RE-S02Y(ST)H-FR / RE-S02YS(ST)H-FR
| No.of pair x | Nominal Cross Sectional Area | No./Nominal Diameter of Strands | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Approx.Weight |
|---|---|---|---|---|---|---|
| mm2 | No/mm | mm | mm | mm | kg/km | |
| 1 | 0.22 | 7/0.2 | 0.55 | 0.40 | 4.6 | 29 |
| 2 | 0.22 | 7/0.2 | 0.55 | 0.40 | 8.1 | 60 |
| 4 | 0.22 | 7/0.2 | 0.55 | 0.40 | 9.6 | 100 |
| 1 | 0.50 | 16/0.2 | 0.55 | 0.40 | 5.2 | 44 |
| 2 | 0.50 | 16/0.2 | 0.55 | 0.40 | 9.3 | 91 |
| 4 | 0.50 | 16/0.2 | 0.55 | 0.40 | 11.1 | 158 |
| 1 | 0.75 | 24/0.2 | 0.55 | 0.40 | 5.6 | 56 |
| 2 | 0.75 | 24/0.2 | 0.55 | 0.40 | 10.3 | 117 |
| 4 | 0.75 | 24/0.2 | 0.55 | 0.40 | 12.2 | 207 |
| 1 | 1.00 | 30/0.2 | 0.55 | 0.40 | 5.8 | 61.4 |
| 2 | 1.00 | 30/0.2 | 0.55 | 0.40 | 10.6 | 128 |
| 4 | 1.00 | 30/0.2 | 0.55 | 0.40 | 12.5 | 228 |
Multipair RS 485 Overall Double Screened Databus Cable
RE-m02Y(ST)CH-FR / RE-m02YS(ST)CH-FR
RE-S02Y(ST)CH-FR / RE-S02YS(ST)CH-FR
| No.of pair x | Nominal Cross Sectional Area | No./Nominal Diameter of Strands | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Approx.Weight |
|---|---|---|---|---|---|---|
| mm2 | No/mm | mm | mm | mm | kg/km | |
| 1 | 0.22 | 7/0.2 | 0.55 | 0.40 | 5.0 | 45 |
| 2 | 0.22 | 7/0.2 | 0.55 | 0.40 | 8.6 | 88 |
| 4 | 0.22 | 7/0.2 | 0.55 | 0.40 | 10.1 | 134 |
| 1 | 0.50 | 16/0.2 | 0.55 | 0.40 | 5.6 | 61 |
| 2 | 0.50 | 16/0.2 | 0.55 | 0.40 | 9.8 | 124 |
| 4 | 0.50 | 16/0.2 | 0.55 | 0.40 | 11.5 | 197 |
| 1 | 0.75 | 24/0.2 | 0.55 | 0.40 | 6.1 | 75 |
| 2 | 0.75 | 24/0.2 | 0.55 | 0.40 | 10.7 | 154 |
| 4 | 0.75 | 24/0.2 | 0.55 | 0.40 | 12.7 | 250 |
| 1 | 1.00 | 30/0.2 | 0.55 | 0.40 | 6.3 | 81 |
| 2 | 1.00 | 30/0.2 | 0.55 | 0.40 | 11.0 | 166 |
| 4 | 1.00 | 30/0.2 | 0.55 | 0.40 | 13.0 | 273 |
Multipair RS 485 Individual & Overall screened Databus Cable
RE-m02Y(ST)H pimf-FR / RE-m02YS(ST)H pimf-FR
RE-S02Y(ST)H pimf-FR / RE-S02YS(ST)H pimf-FR
| No.of pair x | Nominal Cross Sectional Area | No./Nominal Diameter of Strands | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Approx.Weight |
|---|---|---|---|---|---|---|
| mm2 | No/mm | mm | mm | mm | kg/km | |
| 1 | 0.22 | 7/0.2 | 0.55 | 0.40 | 4.9 | 46 |
| 2 | 0.22 | 7/0.2 | 0.55 | 0.40 | 8.6 | 91 |
| 4 | 0.22 | 7/0.2 | 0.55 | 0.40 | 10.1 | 144 |
| 1 | 0.50 | 16/0.2 | 0.55 | 0.40 | 5.5 | 62 |
| 2 | 0.50 | 16/0.2 | 0.55 | 0.40 | 9.8 | 127 |
| 4 | 0.50 | 16/0.2 | 0.55 | 0.40 | 11.6 | 209 |
| 1 | 0.75 | 24/0.2 | 0.55 | 0.40 | 6.0 | 76 |
| 2 | 0.75 | 24/0.2 | 0.55 | 0.40 | 10.7 | 157 |
| 4 | 0.75 | 24/0.2 | 0.55 | 0.40 | 12.7 | 263 |
| 1 | 1.00 | 30/0.2 | 0.55 | 0.40 | 6.2 | 83 |
| 2 | 1.00 | 30/0.2 | 0.55 | 0.40 | 11.0 | 170 |
| 4 | 1.00 | 30/0.2 | 0.55 | 0.40 | 13.0 | 286 |
Multipair RS 485 Overall Screened Databus Cable
RE-m02YCH-FR / RE-m02YSCH-FR
RE-S02YCH-FR / RE-S02YSCH-FR
| No.of pair x | Nominal Cross Sectional Area | No./Nominal Diameter of Strands | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Approx.Weight |
|---|---|---|---|---|---|---|
| mm2 | No/mm | mm | mm | mm | kg/km | |
| 1 | 0.22 | 7/0.2 | 0.55 | 0.40 | 4.8 | 41 |
| 2 | 0.22 | 7/0.2 | 0.55 | 0.40 | 8.4 | 82 |
| 4 | 0.22 | 7/0.2 | 0.55 | 0.40 | 9.9 | 127 |
| 1 | 0.50 | 16/0.2 | 0.55 | 0.40 | 5.4 | 57 |
| 2 | 0.50 | 16/0.2 | 0.55 | 0.40 | 9.6 | 117 |
| 4 | 0.50 | 16/0.2 | 0.55 | 0.40 | 11.4 | 189 |
| 1 | 0.75 | 24/0.2 | 0.55 | 0.40 | 5.9 | 71 |
| 2 | 0.75 | 24/0.2 | 0.55 | 0.40 | 10.5 | 146 |
| 4 | 0.75 | 24/0.2 | 0.55 | 0.40 | 12.4 | 241 |
| 1 | 1.00 | 30/0.2 | 0.55 | 0.40 | 6.0 | 77 |
| 2 | 1.00 | 30/0.2 | 0.55 | 0.40 | 10.8 | 158 |
| 4 | 1.00 | 30/0.2 | 0.55 | 0.40 | 12.8 | 264 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information