Fire Resisting Cable


Fire Resisting Cables


Fire Resistant Coaxial Cables

Fire resistant RG59 B/U Coaxial cables

RG59 B/U FR

Application

The cables are designed for CCTV, security, smoke detection and evacuation monitoring applications, where

continued functionality is required during a fire situation. Due to the zero halogen low smoke construction,

this cable is ideal for use in public, commercial and industrial environments.

Standards

Basic design to MIL-C-17 

Fire resistant RG59 B/U Coaxial cables

Fire Performance

Circuit Integrity

IEC 60331-23; BS 6387 CWZ; DIN VDE 0472-814(FE180);

CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3);

NF C32-070-2.3(CR1)

System circuit integrity DIN 4102-12, E30 depending on lay system

Flame Retardance (Single Vertical

Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C

30-004 (cat. F1); NF C32-070-2.1(C2);

CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation

(Vertically-mounted bundled wires

& cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-

3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-

4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.

Cable Construction

Conductors: Copper clad steel, solid according to IEC(EN) 60228 class 1.

Insulation: PE wrapped with fire resistant silicone rubber compound type EI2 as per BS 7655-1.1 or

fluoropolymer(FEP) compound.

Binder: Glass tape

Overall Screen: Plain copper wire braid

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1(Thermosetting LSZH compound

type SW2-SW4 as per BS 7655-2.6 can be offered.)

Physical And Thermal Properties

Temperature range during operation (fixed state): -30°C - +70°C

Temperature range during installation (mobile state): -5ºC - +60ºC

Minimum bending radius: 8 x Overall Diameter

Electrical Properties

Impedance:75±5Ω

Capacitance:67 nF/km

Velocity ratio(%):66

Insulation resistance :>2000 Mohm.Km

Shield coverage :95%

DC resistance

Inner conductor:158 Ω/km

Outer conductor:9.0 Ω/km

Attenuation

Frequency(MHz) Attenuation (dB/100 m) Attenuation (dB/100ft)
50 7.4 2.26
100 10.7 3.26
200 15.7 4.79
400 22.7 6.92
500 25.7 7.84
600 28.7 8.75
860 34.8 10.61
1000 38.0 11.59

Return Loss

Frequency(MHz) Return Loss (dB)
30-300 MHz >31dB
300-600 MHz >28dB
600-900 MHz >24dB

Construction Parameters

Cable Code Conductor Diameter Nominal Insulation Diameter Nominal Screen No.x Diameter Nominal Overall Diameter Approx. Weight
mm mm No. x mm mm kg/km
RG59 B/U FR 0.58 ± 0.03 3.70 ± 0.10 m 120 x 0.15 6.20 ± 0.10 60.3