      LV
600/1000V ABC –Aerial Bundled Cables to BS 7870-5 (AL/XLPE)
Application
The aerial bundled cables designed for overhead distribution lines have all conductors made of aluminium 1350
and insulated with XLPE. Phase and neutral cores are laid up in a bundle with a left hand lay. Can be used for
fixed installation as overhead power lines up to 1000 V incl.
Standard
BS 7870-5:1999
Construction
Conductor:The conductors shall be of aluminium 1350 wires and are compacted circular stranded(RM).
Insulation:XLPE. 1, 2 and 3 raised longitudinal ribs on the surface of the cores. The surface of the neutral core
should have at least 12 ribs for cross-sections up to 50 mm² and a minimum of 16 ribs for cores above 50 mm².
In the case of five core bundles the surface of the protective core should be smooth.
Assembly:2 up to 4 cores of equal cross section are stranded together in left-hand lay, additionally 1 or 2 cores
of reduced cross section can be co-stranded.
Technical Data
| Rated voltage | kV | 0.6/1 | 
|---|---|---|
| Test voltage | Veff kV | 4 | 
| Laying temperature | °C | min. -20 | 
| Operating temperature | °C | -30 ~ +80 | 
| Conductor temperature | °C | max. +80 | 
| Short-circuit temperature | °C/s | max. +130 /5 | 
| Bending radius (min.) | 
  | 
                          18 × ø of cable | 
Dimensions
| number of cores x nominal cross section | max. conductor- resistance | min. breaking load of conductor strand | Current rating in the air | Outer diameter | Total weight | 
|---|---|---|---|---|---|
| mm² | Ohm/km | kN | A | mm | kg/km | 
| 1x 16 RM | 1,910 | 2,5 | 72 | 80 | 74 | 
| 1x 25 RM | 1,200 | 4,0 | 107 | 90 | 106 | 
| 1x 35 RM | 0,868 | 5,5 | 132 | 105 | 138 | 
| 1x 50 RM | 0,641 | 8,0 | 165 | 118 | 182 | 
| 1x 70 RM | 0,443 | 10,7 | 205 | 130 | 252 | 
| 1x 95 RM | 0,320 | 13,7 | 240 | 154 | 333 | 
| 1x 120 RM | 0,253 | 18,6 | 290 | 170 | 408 | 
| 1x 150 RM | 0,206 | 23,2 | 334 | 190 | 502 | 
| 1x 185 RM | 0,164 | 28,7 | 389 | 210 | 611 | 
| 1x 240 RM | 0,125 | 37,2 | 467 | 240 | 801 | 
| 2x 16 RM | 1,910 | 2,5 | 72 | 156 | 147 | 
| 2x 25 RM | 1,200 | 4,0 | 107 | 180 | 208 | 
| 2x 35 RM | 0,868 | 5,5 | 132 | 200 | 277 | 
| 2x 50 RM | 0,641 | 8,0 | 165 | 235 | 361 | 
| 2x 70 RM | 0,443 | 10,7 | 205 | 254 | 505 | 
| 2x 95 RM | 0,320 | 13,7 | 240 | 303 | 666 | 
| 2x 150 RM | 0,206 | 23,2 | 334 | 380 | 1004 | 
| 4x 16 RM | 1,910 | 2,5 | 72 | 188 | 286 | 
| 4x 25 RM | 1,200 | 4,0 | 107 | 212 | 430 | 
| 4x 35 RM | 0,868 | 5,5 | 132 | 241 | 553 | 
| 4x 50 RM | 0,641 | 8,0 | 165 | 278 | 746 | 
| 4x 70 RM | 0,443 | 10,7 | 205 | 318 | 1009 | 
| 4x 95 RM | 0,320 | 13,7 | 240 | 378 | 1332 | 
| 4x 120 RM | 0,253 | 18,6 | 290 | 544 | 1632 | 
| 4x 50 + 1x 25 RM | 0,641/1,200 | 8,0/4,0 | 165/107 | 319 | 814 | 
| 4x 50 + 1x 35 RM | 0,641/0,868 | 8,5/5,5 | 165/132 | 319 | 845 | 
| 4x 70 + 1x 25 RM | 0,443/1,200 | 10,7/4,0 | 205/107 | 360 | 1105 | 
| 4x 70 + 2x 25 RM | 0,443/1,200 | 10,7/4,0 | 205/107 | 400 | 1217 | 
| 4x 95 + 1x 25 RM | 0,320/1,200 | 13,7/4,0 | 240/107 | 418 | 1438 | 
| 4x 95 + 2x 25 RM | 0,320/1,200 | 13,7/4,0 | 240/107 | 420 | 1544 | 
| 4x120 + 1x 25 RM | 0,253/1,200 | 18,6/4,0 | 290/107 | 590 | 2050 | 
other cross-sections on request