EN50288-7 Cables
XLPE Insulated, LSZH Sheathed Instrumentation Cables

EN 50288-7 Cables

RE-2Y(St)Y 90°C / 300 V

APPLICATION

EN 50288-7 armoured LSZH sheathed cables are generally used when the risk of mechanical damage is

increased. The galvanized steel wire armour provides excellent protection. Generally,EN 50288-7 cables are

used within industrial process manufacturing plants for communication, data and voice transmission signals and

services. Also used for theinterconnection of electrical equipment and instruments, EN 50288-7 LSZH sheath can

reduce toxic smoke and fume emission.

STANDARDS

Basic design to EN 50288-7

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation(Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454
Sunlight Resistance UL 1581 section 1200
Oil Resistance ICEA S-73-532**

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile

strength/min.60% of elongation, *** denotes optional.

VOLTAGE RATING

300V

CABLE CONSTRUCTION

Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation: Extruded cross-linked XLPE compound, EN 50290. 2-29.

Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm

Binder tape: PETP transparent tape

Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with

tinned copper drain wire, 0.5mm²

Inner Sheath: LSZH compound

Amouring: Galvanized steel wire armour

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound

type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti

rodent and anti termite properties can be offered as option.

COLOUR CODE

Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.

Outer Sheath: Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES

Temperature Range During Operation (Fixed State): -30°C – +90°C

Temperature Range During Installation (Mobile State): -5°C – +50°C

Minimum Bending Radius: 6 X Overall Diameter

Electrical PROPERTIES

Conductor Area Size mm² 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C)  Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500

CONSTRUCTION PARAMETERS

 

 

Caledonian Cable Code

RE-2X(St)HSWAH

 

No. of Pairs x2xCross Section

 

Nominal Insulation Thick
-ness

 

Nominal Inner Sheath Thick
-ness

Nominal
Overall Diameter Over Inner Sheath

 

Nominal Armour Wire Diameter

 

Nominal Outer Sheath Thick
-ness

 

No.x2xmm2

mm2

mm

mm

mm

mm

RE-2X(St)HSWAH 1P0.5

1x2x0.50

0.35

0.8

5.2

0.9

1.3

RE-2X(St)HSWAH 1P0.75

1x2x0.75

0.38

0.8

5.6

0.9

1.3

RE-2X(St)HSWAH 1P1.0

1x2x1.0

0.40

0.9

6.3

0.9

1.3

RE-2X(St)HSWAH 1P1.3

1x2x1.3

0.45

0.9

6.8

0.9

1.3

RE-2X(St)HSWAH 1P1.5

1x2x1.5

0.45

0.9

7.1

0.9

1.3

Note : Other conductor sizes & core configurations are available upon request.