Motor Connecting Cables
2YSLCY-JB/2YSLCYK-JB 9YSLCY-JB 9YSLCYK-JB+3 Insulation color code

9YSLCY-JB+3

9YSLCY-JB 9YSLCY-JB

Application

These cables are double shielded, large gauge size, UL/CSA/CE approved PVC motor supply cable.
Polypropylene insulation over very fine stranded copper provides a low-loss transfer of power, excellent
low capacitance performance and superior flexibility when compared to conventional PVC cables. The
applications include frequency converters, motor runs, connections with high electromagnetic interference.
Found in the automotive, paper and food industry, environmental technology, packaging industry,
machine tools and handling equipment. The overall foil and braid shield offer excellent protection against
electromagnetic and electrical interferences. For medium mechanical stresses found indoors in dry, moist and
wet areas. The black UV-resistant jacket allows for outdoor use and for direct burial applications.

Standard and Approval

UL AWM 2570 or 20886, VW-1; CSA AWM I/II A/B, FT-1; UL/CSA rated 1kV 80 Deg C.; VDE 0250, VDE
0207, VDE 0276; EMC to EN 55011; EMC to VDE-0875 part-11; CE Low Voltage Directive 73/23/EEC and
93/68/EEC, ROHS compliant

Cable construction

Stranded bare copper conductor according to DIN VDE 0295, IEC60228 cl. 5
Polypropylene (PP) insulation
Colours according to HD 308 S2(VDE 0293- 308)
Special aluminum foil screening
Three symmetrical green/yellow ground wires
Tinned copper braiding, coverage approx. 85%
Black PVC sheath made of cold-flexible PVC compound DMV5 acc. VDE 0276-603, leadfree, UV resistant,
outdoor and direct burial use, flame retardant & self-extinguishing, IEC 60332.1 EEU directives cables
conforms to EEC 79/29 directive ( Low Voltage Directive)

Technical Characteristics

Working voltage: IEC 600/1000V / UL & CSA 1000V
Test voltage: 4000 volts
Minimum bending radius: 15 x Ø
Flexing temperature: -5º C to +80º C
Fixed installation temperature: - 40º C to +80º C
Flame retardant: IEC 60332.1 VW-1
Insulation resistance: >20 GΩ x km

Cable Parameter

Conductor
AWG
Ground Wire
AWG
No. of Cores x Nominal Cross- Section mm2 Nominal
Overall Diameter mm
Copper Weight kg / km Cable Weight kg / km
16(30/30) 24 3 X 1.5 + 3 G 0.25 11.4 88 140
14(50/30) 22 3 X 2.5 + 3 G 0.5 12.9 130 220
12(56/28) 20 3 X 4 + 3 G 0.75 13.6 224 323
10(84/28) 18 3 X 6 + 3 G 1.0 15.2 276 420
8(80/26) 16 3 X 10 + 3 G 1.5 17.4 511 615
6(128/26) 14 3 X 16 + 3 G 2.5 20 751 819
4(200/26) 12 3 X 25 + 3 G 4 24.3 1204 1325
2(280/26) 10 3 X 35 + 3 G 6 27.5 1535 1718
1(400/26) 8 3 X 50 + 3 G 10 31.1 2156 2399
2/0(356/24) 8 3 X 70 + 3 G 10 37.1 2980 3056
3/0(485/24) 6 3 X 95 + 3 G 16 40 3953 4162
4/0(614/24) 6 3 X 120 + 3 G 16 42.6 4836 5074
300 MCM
(765/24)
4 3 X 150 + 3 G 25 50 5412 6128
350 MCM
(944/24)
2 3 X 185 + 3 G 35 55.6 7077 7820