Instrumentation Cables
1.ESI 0.9-6(1-0.9)
Constructional & Electrical Performance Data
ESI 09-6 Issue 5 Section 2 – Induced Voltage Control Cable
Conductors:
0.90mm Tinned annealed copper wire in accordance with BS6360 Class 1.
Insulation:
The conductors are insulated with Polyvinyl Chloride Type 02 to BS7655, uniformly twisted together to form a pair with a maximum lay length of 125mm, and colour coded for identification (See Table 1). Suitable for voltages up to and including 150 Volts (d.c.) and 110 Volts (a.c.)
Cable Formation:
2 pair cables are laid up in quad formation.
5 – 100 pair cables are laid up in layer formation.
Screens
All cables, if required, can incorporate a screen comprising of an aluminium/PETP tape.
The tape screen is in contact with a 0.80mm tinned copper drain wire.
Outer Coverings
Type 1 | Unarmoured Multipair Light Current Control cables. Extruded Polyvinyl Chloride sheath to BS7655. |
---|---|
Type 2 | Armoured Multipair Light Current Control cables. Extruded Polyvinyl Chloride bedding to BS7655, Galvanised steel wire armour to BS1442 and an extruded Polyvinyl Chloride sheath to BS7655. |
Alternative PVC materials producing lower levels of HCL are available on request.
Electrical Characteristics
High Voltage Test | ||
---|---|---|
Collective screens | 2000 Volts for 1 minute between each conductors & earth | |
Cables without screen | 5000 Volts for 1 minute between all conductors & earth | |
Conductor Resistance | 59.34 Ohm/Km Loop @ 20°C (Max) | |
Insulation Resistance | 80 MOhm/Km @ 20°C (Min) |
Cable Dimensions & Identification
Type 1 cables (Unarmoured)
Type 2 (Armoured)
Table 1 Identification of pairs