Mineral insulated cables
Constant Wattage Heating Cable up to 200 °C
Application:
Vessels, piping, valves
Food processing industry
Frost protection and temperature maintenance on pumps
Standard:
IEC 62395-2, EN 60519-10.
Voltage Rating:
230V
CABLE CONSTRUCTION:
Bus wire
Insulation: Silicone.
Heating conductor
Protective: Copper braid
Outer sheath: Silicone.
Mechanical and Thermal Properties:
Nominal temperature: 200℃
Minimum installation temperature: -60℃
Minimum start-up temperature: -60℃
Bus wire cross section: 2x1.50 mm²
Cable Parameter:
APPROX. Dimensions mm |
Contact spacing m | Nominal output W/m | Maximum heating circuit length m | |
---|---|---|---|---|
at 50 °C | at 150 °C | |||
5.25x9.75 |
1.0 |
10 |
198 |
147 |
5.25x9.75 |
1.0 |
20 |
139 |
102.5 |
5.25x9.75 |
1.0 |
30 |
98 |
82.5 |
5.25x9.75 |
1.0 |
40 |
73.5 |
70.5 |