HOMEPRODUCTSOTHER CABLE

 

Mineral insulated cables

Heating Tape for Sensitive Surfaces

 

 

 

Application:

Heat tracing on apparatus, appliances and systems

Temperature maintenance on piping

Laboratory applications

Standard:

DIN VDE 0253

Voltage Rating:

230V

CABLE CONSTRUCTION:

Heating conductor

Insulation: Fluoropolymer.

Protective: Nickel-plated copper.

Outer sheath: E-glass textile.

Mechanical and Thermal Properties:

Maximum operating temperature: 260℃

Minimum installation temperature: -60℃

Minimum bending radius flat: 10 mm

Maximum output: 50 W/m

Approx Dimensions : 25 x 6 mm

Cable Parameter:

Heated length m Nominal output W
Maximum temperature 100 °C Maximum temperature 150 °C Maximum temperature 200 °C

0.6

30

-

-

1.1

54

-

-

1.7

78

52

26

2.4

94

69

37

3.0

147

88

44

4.2

210

126

63

5.4

245

163

82

6.0

294

176

88

7.0

344

-

-

10.0

464

294

-

12.5

623

371

192

15.0

705

441

220

17.5

864

521

-

21.0

1008

611

315

28.0

1390

756

378