Industrial Cables
Spanish Standard Industrial Cables
RHVMV
Application and Description:
This 3 conductor cable can be used for indoor and outdoor applications consists of three phases, usually used in power networks, it also can be Installed in conduit and direct burial.
Standard and Approval :
IEC 60502, IEC 60332-3-24(C)
Cable Construction:
- Compacted copper strands conductor
- Stands to IEC 60228 Class 2
- Semi-conducting conductor screen
- XLPE insulation according to IEC 60502
- Semi-conducting insulation screen
- Individual copper wire and tape screen
- PP fiber and PP tape filling
- Binder tape
- Extruded continuous PVC bedding type ST2 of standard IEC 60502
- Galvanized steel wire armour
- Flexible special PVC compound outer sheath type ST2 of standard IEC 60502
Technical Characteristics:
- Working voltage: 6/10 KV
- Test voltage: 75 KV
- Minimum bending radius: 10 x Ø(fixed installation)
15x Ø(during operation)
- Working temperature: -10º C to +90º C
- Short circuit temperature: +250º C
- Flame retardant: IEC 60332.3
- Insulation resistance: 20 MΩ x km
Cable Parameter:
AWG | No. of Cores x Nominal Cross Sectional Area # x mm² |
Nominal Thickness of Insulation mm |
Nominal Diameter over Insulation mm |
Nominal Diameter over Bedding mm |
Nominal Steel Wire Armour Diameter mm |
Nominal Overall Diameter mm | Nominal Weight kg/km |
---|---|---|---|---|---|---|---|
2/0 | 3 x 70.0 | 3.4 | 17.8 | 49.8 | 2.5 | 60.5 | 6650 |
3/0 | 3 x 95.0 | 3.4 | 19.5 | 53.4 | 2.5 | 64.0 | 7750 |
4/0 | 3 x 120.0 | 3.4 | 20.8 | 56.4 | 2.5 | 67.5 | 8800 |
350MCM | 3 x 185.0 | 3.4 | 24.1 | 63.8 | 3.15 | 77.0 | 12250 |
500MCM | 3 x 240.0 | 3.4 | 26.3 | 68.5 | 3.15 | 82.0 | 14450 |