HOMEPRODUCTS FIRE RESISTING CABLES(FIREFLIX)

 

 

Fire Resistant Optic Fiber Cables

Fire Resistant Tight Buffered Distribution Fiber Optic cables

MTA-B-C-D-H-FR

 


Application:

This cables are used for interconnection of distribution boxes and end devices, where continued functionality is required during a fire situation. The cables are very suitable for various indoor and outdoor applications, including routing between buildings within ducts and inside building up to riser shafts.

Standards :

Basic design to Telcordia GR409-CORE / TIA/EIA 568B.3 / ICEA-S-83-596

Fire Resistant Tight Buffered Distribution Fiber Optic cables

Fire Pefeormance:

Circuit Integrity

IEC 60331-25; BS 6387 CWZ; DIN VDE 0472-814(FE180);

CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3);

NF C32-070-2.3(CR1)

System circuit integrity

DIN 4102-12, E30 depending on lay system

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C

30-004 (cat. F1); NF C32-070-2.1(C2);

CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-

3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-

4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.

Cable Construction:

Optical fibers: Singlemode and multimode tight fibers, with tight buffer coating.

Fire Barrier: The tight buffered fibers are wrapped with fire blocking fiber glass yarns.

Inner Sheath(optional): Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1

Ripcord(optional): An optional ripcord can be located under the outer sheath to facilitate jacket removal.

Armouring(optional):

STA: Corrugated steel tape armour

SWB: Steel wire braid

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)

Physical and thermal properties:

Temperature range during operation (fixed state): -20°C - +60°C

Temperature range during installation (mobile state): 0°C - +50°C

Minimum bending radius: 10 times the outer diameter for unarmoured cables

                                         20 times the outer diameter for armoured cables

Construction Parameters:

Cable Code N° of Fibers Nominal Overall Diameter Max Tensile Strength Minimum bending radius Approx.Weight
mm N mm kg/km
MTA-B-2-0-H-FR 2 7,6 250 76 55
MTA-B-4-0-H-FR 4 7,8 250 78 67
MTA-B-6-0-H-FR 6 8,6 400 86 77
MTA-B-8-0-H-FR 8 8,8 400 88 81
MTA-B-12-0-H-FR 12 9,3 400 93 90