Fire Resisting Cables
Fire resistant RG6 QUAD Coaxial cables
RG6 QUAD FR
Application:
The cables are designed for CCTV, security, smoke detection and evacuation monitoring applications, where continued functionality is required during a fire situation. Due to the zero halogen low smoke construction, this cable is ideal for use in public, commercial and industrial environments.
Standards:
Basic design to MIL-C-17

Fire Performance:
| Circuit Integrity | IEC 60331-23; BS 6387 CWZ; DIN VDE 0472-814(FE180); CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) |
|---|---|
| System circuit integrity | DIN 4102-12, E30 depending on lay system |
| Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
| Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332- 3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2- 4*; DIN VDE 0482-266-2-4 |
| Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
| No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
| Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
| No Toxic gases | NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
Cable Construction:
Conductors: Copper clad steel, solid according to IEC(EN) 60228 class 1.
Insulation: Foamed PE wrapped with fire resistant silicone rubber compound type EI2 as per BS 7655-1.1 or fluoropolymer(FEP) compound.
Binder: Glass tape
Overall Screen:
Screen1: Al-maylar Tape ≥25%
Screen2: Aluminium Braid
Screen3: Al-maylar Tape ≥25%
Screen4: Aluminium Braid
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
Physical And Thermal Properties:
Temperature range during operation (fixed state): -30°C - +70°C
Temperature range during installation (mobile state): -5ºC - +60ºC
Minimum bending radius: 8 x Overall Diameter
Electrical Properties:
Impedance:75±5Ω
Capacitance:54 nF/km
Velocity ratio(%):82
Insulation resistance :>5000 Mohm.Km
Shield coverage :≥60%
Max.conductor resistance:24.1 Ω/km
Attenuation:
| Frequency(MHz) | Attenuation (dB/100 m) | Attenuation (dB/100ft) |
|---|---|---|
| 50 | 4.8 | 1.5 |
| 100 | 6.7 | 2.0 |
| 200 | 9.3 | 2.8 |
| 500 | 15.0 | 4.6 |
| 600 | 16.9 | 5.1 |
| 800 | 19.4 | 5.9 |
| 1000 | 21.6 | 6.6 |
| 1350 | 24.2 | 7.4 |
| 1750 | 28.0 | 8.4 |
| 2150 | 31.5 | 9.6 |
| 2400 | 32.8 | 10.0 |
| 3000 | 37.9 | 11.5 |
Return Loss:
| Frequency(MHz) | Return Loss (dB) |
|---|---|
| 30-300 | >28dB |
| 300-600 | >24dB |
| 600-900 | >22dB |
Construction Parameters:
| Cable Code | Conductor Diameter | Nominal Insulation Diameter | Nominal Screen2 No.x Diameter | Nominal Screen4 No.x Diameter | Nominal Overall Diameter | Approx. Weight |
|---|---|---|---|---|---|---|
| mm | mm | No. x mm | No. x mm | mm | kg/km | |
| RG6 QUAD FR | 1.02 | 4.60 ± 0.20 | 80 x 0.12 | 64 x 0.12 | 7.55 ± 0.20 | 92.4 |