CPR/Fire-safety cable
CPR Introduction
3. Relevant Euro Classes for different Environments & EU countries.
The regulation assigns seven (7) “EuroClass/reaction to fire” levels, ranging from ‘Aca’ to ‘Fca’ The CPR ranking highest to lowest are: Aca; B1ca; B2ca; Cca; Dca; Eca and Fca. The ‘ca’ tag on the letter indicates cable. Classes are listed from the most stringent ‘A’, non-combustible, to ‘F’. For telecommunication cables, the best performance you’re likely to see is B2ca. Typically, EuroClasses are assigned based on the application space/structure type. Structures with a high density of people (public spaces) or limited evacuation routes (hospitals/high rise) may specify a higher rated classification e.g. hospitals may be rated as B2ca or Cca; commercial properties may be Cca or Dca; while a single family dwelling may be Dca or Eca. This varies from country to country and even within country regions.
| Euroclass Level | Description | Environments |
|---|---|---|
| B2ca |
Very High fire protection (self-extinguishing) |
High density of people or individuals with limited mobility (Fire exits in public building, |
| Cca | High Fire protection |
Medium density of people |
| Dca | Moderate Fire Protection |
In some regions this is used a |
| Eca | Basic Fire Protection |
In some regions this is used a |
CPR is mandatory for all European countries, but the minimum CPR requirements may vary from country to country. Some countries have implemented a minimum classification and some countries have adopted a risk assessment methodology based on the type of installation or its fire suppression system.
Different classes require different criteria to be applied. Therefore, cables will be made and tested to achieve the requirements of a particular class. It is not just the way they’re made and tested, it involves who tested them and how the manufacturing process is controlled. Cable cannot simply “jump up class” by tweaking the manufacturing or doing some more tests. Class B1ca cable could be sold as Class Cca (as Class B1ca is superior to Class Cca), but Class Cca cannot be sold as.
Class B1ca.
| Countries | Installation Conditions | CPR Requirement as of 1st July 2017 |
|---|---|---|
| Belgium | F2:Cables in bundles and in vertical position which |
Cca, S1, a1 |
F1: Cables simply laid and in the test conditions that do not propagate the flame and extinguish themselves within a short distance of the fire that |
Eca minimum |
|
| Denmark | All areas |
Eca |
| Finland | Local Wiring Regulations |
Eca |
Buildings with a high density of people |
Dca |
|
| France | Underground stations and tunnels |
B2ca, s1a,d1,a1 |
Very high rise buildings |
Cca,s1,d1,a1 |
|
Offices with height >28m |
||
Offices having >700 people |
||
Data Centers and Server/Routing Rooms |
||
All others |
Dca,s2,d2,a2 |
|
| Germany | All evacuation routes |
B2ca,s1,d1,a1 |
Data Centers & Server Rooms |
||
Rail / Road tunnels |
||
Hospitals |
||
All others |
Cca,s1,d2,a1 |
|
| Iceland | All evacuation routes |
Cca,s1,d1,a1 |
All others |
Dca,s2,d2 |
|
Spaces equipped with a fire alarm or an automatic |
|
|
| Ireland | Likely to follow UK |
|
| Italy | Train and Underground Stations |
B2ca,s1a,d1,a1 |
Airports, Seaports |
Cca,s1b,d1,a1 |
|
Hospitals |
||
Hotels |
||
Schools |
||
Offices having >300 people |
||
Retail, Conference centres |
||
Government Buildings >24m |
||
All others |
Cca,s3,d1,a3 |
|
| Netherlands | Hospitals >500m2 |
B2ca,s1,d1,a1 |
Tunnels >500m2 |
||
Protected evacuation routes |
Cca,s1,d1,a1 |
|
Buildings with >500 people |
||
All others |
Dca,s3,d2,a3 |
|
| Norway | All areas |
Dca |
With automatic fire suppression installed |
Eca |
| Countries | Installation Conditions | CPR Requirement as of 1st July 2017 |
|---|---|---|
| Poland (patch cords are included in CPR) |
Public Buildings |
Dca,s2,d2,a1 |
Non-public buildings |
Eca |
|
| Spain | All areas |
Cca,s1b,d1,a1 |
| Sweden | All areas |
Dca |
| Switzerland | Government buildings escape routes |
Cca,s2,d1,a2 |
Government buildings other areas |
Dca |
|
Non-government buildings escape routes |
Dca,s2,d1,a2 |
|
Non-government buildings other areas |
Eca |
|
| Turkey | Data Centers |
B2ca,s1,d0,a1 |
Exhibition Centers |
||
Rail/Road tunnels |
B2ca,s1,d1,a1 |
|
Hospitals |
||
All escape routes |
||
Hotels, height >30.5m |
||
High rise buildings ≥ 21.5 m |
||
All others |
Cca,s1,d2,a1 |
|
| UK | BS 7671: IET wiring Regulations, 18th Edition |
CPR is referred to in an |
Escape Routes |
BS 6701 for data cables & Dca,s2,d2,a2 for power |
|
BS 6701: Bundled telecommunications “installation |
Cca,s1,d2,a2 |
|
BS 6701: All other telecommunications cables |
Eca |
Note: Always check with local building control authorities and refer to national regulations.