Mining Cable
Type W Type G Type G-GC more

Mining Cable

Type W Four-Conductor Flat Portable Power Cable 2kV

Applications

Type W Four-Conductor Flat Portable Power Cables are designed for general use where baregrounding

conductors are not required ordesired.

Standards

ICEA S-75-381/NEMA WC 58

ASTM B 172

ASTM B 33

CAN/CSA C22.2 No. 96

Construction

Type W Four-Conductor Flat Portable Power Cable 2kV

Conductors: Stranded annealed tinned copper conductor.

Insulation:EPR.

Sheath: Reinforced extra-heavy-duty Chlorinated Polyethylene(CPE), black. Other sheath materials can be

offered upon request.

Options:

Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.

Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.

Mechanical and Thermal Properties

Minimum Bending Radius: 6×OD

Maximum Operating Temperature: +90℃

Dimensions and Weight:

Construction No. of Strands Nominal Insulation Thickness Nominal Overall Diameter Nominal Weight Ampacity
No. of cores×AWG/kcmil inch mm inch mm lbs/kft kg/km A
2×8 166 0.06 1.5 0.83 21.1 391 581 72
2×6 259 0.06 1.5 0.94 23.9 571 849 95
2×4 412 0.06 1.5 1.07 27.3 793 1180 127
2×2 259 0.06 1.5 1.26 32.1 1142 1699 167
2×1/0 414 0.08 2.0 1.51 38.3 1693 2520 217
2×2/0 522 0.08 2.0 1.65 41.9 1908 2840 250
2×3/0 658 0.08 2.0 1.77 45.0 2600 3870 286
2×4/0 829 0.08 2.0 1.92 48.8 2675 3980 328
2×250 973 0.095 2.4 2.10 53.3 3434 5110 363

Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.

Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information