Industrial Cables  
H03VV-F H05VV-F H07RN-F more

Industrial Cables

H05V-K

Application and Description

H05V-K cables are determined for installation to the inside of apparatus as well as for the protective laying to

the lightings, in dry rooms, in production facilities, switch and distributors boards, in tubes, under and surface

mounting of plasters.

Standard and Approval

HD 21.3 S3, VDE-0281 Part-3

Cable Construction

Fine bare copper strands

Strands to VDE-0295 Class-5, IEC 60228 Class-5

Special PVC TI1 core insulation

Cores to VDE-0293 colors on chart

Technical Characteristics

Working voltage: 300/500v

Test voltage: 2000 volts

Flexing bending radius: 12.5 x Ø

Static bending radius: 12.5 x Ø

Flexing temperature: -5º C to +70º C

Static temperature: -30º C to +80º C

Flame retardant: IEC 60332.1

Insulation resistance: 10 MΩ x km

H05V-K H05V-K

Cable Parameter

AWG No. of Cores x Nominal Cross Sectional Area # x mm² Nominal Thickness of Insulation mm Nominal Overall Diameter mm Nominal Copper Weight kg/Km Nominal Weight kg/Km
20(16/32) 1 x 0.5 0,6 2.1 4.9 10
18(24/32) 1 x 0.75 0,6 2.4 7.2 13
17(32/32) 1 x 1 0,6 2.6 9.6 15