Industrial Cables  
H03VV-F H05VV-F H07RN-F more

Industrial Cables Single Core Fixed Wiring Cable

6591TQ to BS 6883

Application and Description

6591TQ to BS 6883 cables are designed for use in offshore applications where mechanical protection is not

required. Examples of application include fixed wiring in ships and fixed offshore drilling rigs and oil platforms.

Cable Construction

Fine bare copper strands

Stranding to BS 6360 Class 2 or IEC 60228 Class 2

EPR(Ethylene Propylene Rubber) rubber insulation to BS 6899, white

TPBWB (Tinned phosphor bronze wire braid) non-magnetic armour

LSOH (Low Smoke Zero Halogen), type SW4 to BS 6899

Technical Characteristics

Working voltage: 600/1000 volts

Test voltage: 2000 volts

Minimum bending radius: up to 10mm² 3xOverall diameter

10mm²-25mm² 4xOverall diameter

Above 25mm² 6xOverall diameter

Temperature Range: -25º C to +85º C

Oxygen Index32%, HCL 5%

Flame retardant: IEC 60332.1

Insulation resistance: 20 MΩxkm

Cable Parameter

AWG (No of Strands/ Strand Diameter) No. of Cores x Nominal Cross Sectional Area
#xmm²
Nominal Thickness of Insulation
mm
Nominal Thickness of
Bedding
mm
Diameter of Braid Wire
mm
Nominal Thickness of Sheath
mm
Nominal Overall Diameter
mm
Nominal Weight kg/km
17(7/26) 1x1.0 0.8 1 0.3 1 8.8 135
16(7/24) 1x1.5 0.8 1 0.3 1.1 9.3 145
14(7/22) 1x2.5 0.8 1 0.3 1.1 9.8 165
12(7/20) 1x4 1 1 0.3 1.1 10.8 190
10(7/18) 1x6 1 1 0.3 1.1 11.4 225
8(7/16) 1x10 1 1 0.3 1.2 13.1 315
6(7/14) 1x16 1 1 0.3 1.2 14.2 395
4(7/12) 1x25 1.2 1.2 0.3 1.3 16.7 565
2(7/10) 1x35 1.2 1.2 0.3 1.4 17.8 670
1(19/13) 1x50 1.4 1.4 0.3 1.4 19.7 865
2/0(19/11) 1x70 1.4 1.4 0.3 1.5 22.1 1120
3/0(19/10) 1x95 1.6 1.6 0.3 1.6 24.4 1440
4/0(37/12) 1x120 1.6 1.6 0.3 1.7 26.6 1780
300MCM
(37/11)
1x150 1.8 1.8 0.3 1.8 28.9 2120
350MCM
(37/10)
1x185 2 2 0.45 1.9 32.5 2700
500MCM
(61/11)
1x240 2.2 2.2 0.45 2 36 3410
(61/10) 1x300 2.4 2.4 0.45 2.2 39.4 4180
(61/9) 1x400 2.6 2.6 0.45 2.3 43.9 5280
(61/8) 1x500 2.8 2.8 0.45 2.5 48.1 6480
(127/10) 1x630 2.8 2.8 0.45 2.6 52.3 7820