Airport Cable  
 

 FAS (Fire Alarm System)

RS485 Data Cable RE-02Y(St)H 1P18A

RE-02Y(St)H 1P18A (CU/PE/OSCR/LSZH 1×2×18AWG)
RE-02Y(St)H 1P18A (CU/PE/OSCR/LSZH 1×2×18AWG)     

Applications

Airprot cables are designed for RS485 data connections. Airprot cable combines low capacitance insulation with

one of the highest levels of screening to provide high speed, interference free, data transmission where

continued functionality is required during a fire situation.

Standards

Basic design :EIA/TIA 485

Halogen Free :IEC 60754-1

No corrosive gas emission :IEC 60754-2

Minimum Smoke Emission :IEC 61034-1/2

Reduced Fire Propagation :IEC 60332-3C / NF C 32070-2.2 (C1)

Flame Retardance :IEC 60332-1 / NF C 32-070-2.1 (C2)

Fire Resistance :IEC 60331-23 / NF C 32-070-2.3(CR1)

Construction

Conductors: tinned annealed copper wire, stranded according to IEC(EN) 60228 class 2 or class 5.

Insulation: Solid or foam PE compound

Cabling Elements: Insulated cores are twisted to form pairs with varying lay length to minimize crosstalk.

Overall screen: Aluminum/ polyester tape with tinned copper drain wire.

Fire Barrier: Fireproof Tape.

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1.

Electrical PROPERTIES

Dielectric test:1000 V r.m.s. for 5’ (core-core)

                         1000 V r.m.s. for 5’ (core-screen)

Impedance:120Ω

Capacitance:45 nF/km conductor to conductor

                     90 nF/km conductor to shield

Physical AND THERMAL PROPERTIES

Temperature range during operation (fixed state): -30°C – +90°C

Temperature range during installation (mobile state): -20°C – +50°C

Minimum bending radius: 8 × Overall Diameter

CONSTRUCTION PARAMETERS

RE-02Y(ST)H 1P18A

No.of pair × Wire
Gange
Number &
Nominal Diameter of Strands
Nominal Insulation Thickness Nominal Sheath Thickness Nominal Overall Diameter Approx.Weight
  AWG No/mm mm mm mm kg/km
1 18 7/0.404 1.15 1.2 10.5 100
1 18 16/0.254 1.15 1.2 10.5 100