APPLICATION
Airprot cables are designed for CCTV, security, smoke detection and evacuation monitoring applications, where continued functionality is required during a fire situation. Due to the zero halogen low smoke construction, this cable is ideal for use in public, commercial and industrial environments.
STANDARDS
Basic design to MIL-C-17
FIRE PERFORMANCE

FlameRetardance (SingleVerticalWireTest)** EN60332-1-2; IEC60332-1-2; BSEN 60332-1-2; VDE0482-332-1; NBN C30-004 (cat.F1);NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced FirePropagation(Vertically-mountedbundledwires &cabletest)** EN60332-3-24(cat.C); IEC60332-3-24;BSEN60332-3-24;VDE0482-332-3;NBN C30-004 (cat.F2);NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Note:
Asterisk * denotes superseded standard
Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC
compound and the cable design.
CABLE CONSTRUCTION
Inner conductor: Copper clad steel
Insulation: Foam PE
Screen 1: Al-maylar
Screen 2: AL braid
Screen 3: Al-maylar
Screen 4: AL braid
Outer Sheath: Thermoplastic PVC compound.
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C - +70°C
Temperature range during installation (mobile state): -5ºC - +60ºC
Minimum bending radius: 8 x Overall Diameter
Electrical Properties

Impedance 75±5 OHM
Capacitance 54NF/kM
Velocityratio(%) 82
Insulationresistance >5000Mohm.km
Shieldcoverage 60%/40%
DC resistance  
Conductor resistance ≤24.1Ω/km

Attenuation

Frequency(MHz) Attenuation(dB/100m) Attenuation(dB/100ft)
50 4.8 1.5
100 6.7 2.0
200 9.3 2.8
500 15.0 4.6
600 16.9 5.1
800 19.4 5.9
1000 21.6 6.6
1350 24.2 7.4
1750 28.0 8.4
2150 31.5 9.6
2400 32.8 10.0
3000 37.9 11.5

CONSTRUCTION PARAMETERS

CableCode ConductorDiameter NominalInsulation Diameter NominalScreen No.xDiameter NominalOverall Diameter Approx. Weight
  mm mm No. x mm mm kg/km
RG6/U Quad 1.02 4.8 80x0.12/64x0.12 7.55 59.8