| Thermocouple Cables | |||
| single pair | multipair |
Thermocouple Cable EX, JX, KX, TX
600V, 90oC Wet or Dry
Application:
For use as a 600 Volt, multi-pair thermocouple instrumentation cable where flame-retardance, and
moisture/chemical resistance is critical. Cable can be installed in free air, in raceways, or direct burial. The cable
is also approved for wet or dry locations as well as Class 1 Division II industrial hazardous locations per NEC
501-4(b) for (UL) Type Tray Cables (TC).
Temperature rating of 90oC wet or dry. Insulation provides excellent electrical, thermal, and physical properties,
excellent flame resistance and resistant to crush, compression, cuts and heat deformation. Also conductor
insulation provides good low temperature (-40oC) cold bend characteristics.
Approved for direct burial.
Construction:
Conductor is thermocouple alloy per ANSI MC96.1 - 1982.
Extruded flame-retardant ethylene propylene rubber (EPR) insulation.
Conductors twisted together with a drain wire and aluminum mylar shield. Shielded pairs cabled together with
fillers as needed to form a round core. An overall aluminum mylar shield and drain wire is applied over the core.
Pairs are color coded per thermocouple type with pair number printed on the negative (red) conductor. See chart
below for specific color codes.
Black, flame-retardant, sunlight resistant, Chlorinated Polyethylene (CPE) jacket. Available with color coded
jacket.
Available with class B stranding per ASTM B174.
Standards:
Insulated Conductor - VW-1.
UL Type TC, 90oC Wet or Dry, 600V
ICEA S-82-552, 90oC Wet or Dry, 600V.
Passes UL 1277 Flame Test (70,000 BTU/hr).
Passes UL 1202 Flame Test (70,000 BTU/hr).
Passes IEEE 383 Flame Test (70,000 BTU/hr).
Passes ICEA T-29-520 Flame Test (210,000 BTU/hr).
EX - Color Code
Chromel (Positive) - PURPLE
Constantan (Negative) - RED
JX - Color Code
Iron (Positive) - WHITE
Constantan (Negative) - RED
TX - Color Code
Copper (Positive) - BLUE
Constantan (Negative) - RED
KX - Color Code
- Chromel (Positive) - YELLOW
Alumel (Negative) - RED
-
Item # Number of
Shielded PairsInsulation Thickness
(mils)Jacket Thickness
(mls)Overall
Diameter
(inches)Weight
LBS/MFTITC-20-1 1 0.025 0.045 0.270 35 ITC-20-2 2 0.025 0.045 0.035 70 ITC-20-3 3 0.025 0.045 0.450 85 ITC-20-4 4 0.025 0.045 0.500 105 ITC-20-6 6 0.025 0.045 0.600 160 ITC-20-8 8 0.025 0.045 0.670 210 ITC-20-10 10 0.025 0.045 0.735 240 ITC-20-12 12 0.025 0.045 0.790 280 ITC-20-16 16 0.025 0.045 0.890 360 ITC-20-24 24 0.025 0.045 1.060 500 ITC-18-1 1 0.025 0.045 0.300 50 ITC-18-2 2 0.025 0.045 0.480 90 ITC-18-3 3 0.025 0.045 0.510 115 ITC-18-4 4 0.025 0.045 0.595 165 ITC-18-6 6 0.025 0.045 0.670 220 ITC-18-8 8 0.025 0.045 0.750 280 ITC-18-10 10 0.025 0.045 0.820 340 ITC-18-12 12 0.025 0.045 0.930 430 ITC-18-16 16 0.025 0.045 1.045 540 ITC-18-24 24 0.025 0.045 1.235 760 ITC-16-1 1 0.025 0.045 0.325 60 ITC-16-2 2 0.025 0.045 0.570 130 ITC-16-3 3 0.025 0.045 0.600 160 ITC-16-4 4 0.025 0.045 0.660 200 ITC-16-6 6 0.025 0.045 0.740 270 ITC-16-8 8 0.025 0.045 0.880 380 ITC-16-10 10 0.025 0.045 0.970 460 ITC-16-12 12 0.025 0.045 1.035 530 ITC-16-16 16 0.025 0.045 1.165 570 ITC-16-24 24 0.025 0.045 1.400 960