Power Distribution Cables
600/1000V Single conductor Type P distribution cables
Construction
Conductor: Stranded copper conductor tin or alloy coated where necessary for the application , conductor per
ASTM or IEC 60228.
Separator tape: optional
Insulation: Cross-linked polyolefin(XLPO)according to IEEE 1580 2010 Type P,Type X, E, T, T/N, S, P, LSX and
LSE as option.
Shielding: optional
Jacket: Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N, Type T, CP, CPE, L, P or
TPO jacket as option (optional for Type P with HD thicknesses).
Armor: optional and shall be nonmagnetic
Sheath: Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N, Type T, CP, CPE, L, P
or TPO sheath as option (optional except for tinned copper braid armoured cables).
Optional: For halogen-free constructions, Type LSX, LSE or LSS insulation shall be used with a Type L or TPO
jacket/sheath.
Table B.4—Typical dimensions and weights; single conductor 2000 V; Type P distribution cables
Conductor size in AWG or kcmil |
Unarmored | Armored | Armored and sheathed | |||
|---|---|---|---|---|---|---|
| Nom. dia. (in) | Approx. weight (lb/1000 ft) | Nom. dia. (in) | Approx. weight (lb/1000 ft) | Nom. dia. (in) | Approx. weight (lb/1000 ft) | |
18 |
0.143 | 16 | 0.193 | 29 | 0.324 | 38 |
16 |
0.153 | 18 | 0.203 | 32 | 0.334 | 42 |
14 |
0.168 | 25 | 0.218 | 45 | 0.349 | 60 |
12 |
0.187 | 32 | 0.237 | 58 | 0.368 | 80 |
10 |
0.207 | 51 | 0.257 | 93 | 0.388 | 127 |
8 |
0.255 | 71 | 0.305 | 116 | 0.436 | 159 |
6 |
0.295 | 108 | 0.345 | 155 | 0.476 | 204 |
4 |
0.377 | 173 | 0.427 | 230 | 0.558 | 296 |
2 |
0.443 | 242 | 0.493 | 303 | 0.624 | 366 |
1 |
0.484 | 335 | 0.534 | 406 | 0.665 | 468 |
1/0 |
0.548 | 420 | 0.598 | 494 | 0.729 | 571 |
2/0 |
0.615 | 494 | 0.665 | 579 | 0.796 | 662 |
3/0 |
0.663 | 734 | 0.713 | 776 | 0.886 | 900 |
4/0 |
0.729 | 820 | 0.779 | 889 | 0.952 | 1036 |
262 kcmil |
0.888 | 945 | 0.938 | 1147 | 1.111 | 1295 |
313 kcmil |
0.954 | 1113 | 1.004 | 1332 | 1.177 | 1491 |
373 kcmil |
1.018 | 1419 | 1.068 | 1576 | 1.241 | 1741 |
444 kcmil |
1.094 | 1578 | 1.144 | 1816 | 1.317 | 1992 |
535 kcmil |
1.212 | 1976 | 1.262 | 2246 | 1.435 | 2425 |
646 kcmil |
1.3 | 2348 | 1.35 | 2559 | 1.523 | 2757 |
777 kcmil |
1.395 | 2795 | 1.445 | 3013 | 1.618 | 3205 |
1111kcmil |
1.652 | 3982 | 1.702 | 4129 | 1.938 | 4484 |
NOTE—These values are for reference purposes only and should not be construed as requirements.
Weights of armored constructions are based on bronze braid armor. It is recommended that the user/
specifier contact the manufacturer for manufacturer specific values.
The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information