Firetox Flame Retardant Cables 

Firetox Flame Retardant Cables

450/750V XLPE Insulated, LSZH Sheathed, Screened Power Cables (2-4cores)

FTX200 07RCZ1-R (CU/XLPE/CUTO/LSZH 450/750V Class 2)

Application

450/750V XLPE Insulated, LSZH Sheathed, Screened Power Cables (2-4cores) are mainly used in power

stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and

high-rise buildings.

Standards

Basic design to BS 7211; IEC 60502-1

450/750V XLPE Insulated, LSZH Sheathed, Screened Power Cables (2-4cores)

Fire Performance

Flame Retardance

(Single Vertical

Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE

0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-

1*; DIN VDE 0482-265-2-1*

Reduced Fire

Propagation

(Vertically-mounted

bundled wires

& cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-

004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-

4

Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas

Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*

minimum Smoke

Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-

1&2*; BS 7622-1&2*

No Toxic gases NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.

Voltage Rating

450/750V

Cable Construction

Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.

Insulation: Extruded cross-linked XLPE compound.

Filler, binder (if any): PP, PET, LSZH

Overall Screen: Copper tape

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound

type SW2-SW4 as per BS 7655-2.6 can be offered.)

Colour Code

Insulation colour as per bs7671

  with earth conductor without earth conductor
2Cores - Brown,Blue
3Cores Yellow/Green,Brown,Blue Brown,Gray,Black
4Cores Yellow/Green,Brown,Gray,Black Brown,Gray,Black,Blue
5Cores Yellow/Green,Brown,Gray,Black,Blue Brown,Gray,Black,Blue,Black
above 5 Cores Yellow/Green,Black Numbered Black Numbered

sheath colour: Black

Physical And Thermal Properties

Temperature range during operation: Max.90°C for XLPE

250°C in short-circuit for 5s max.

Minimum bending radius: 6 x Overall Diameter

Construction Parameters

Conductor FTx200 07RcZ1-R
No. of Core X Cross Section No./ Nominal Diameter of Strands Nominal Overall Diameter Conductor Nominal Insulation Thickness Nominal Copper Tape Thickness Nominal Sheath Thickness Nominal Overall Diameter max.DC resistance of conductor
@20°C
Approx. Weight
Noxmm2 No./mm mm mm mm mm mm Ω/km kg/km
2x1.0 7/0.44 1.32 0.7 0.1 1.2 10.7 18.1 172
2x1.5 7/0.53 1.59 0.7 0.1 1.3 11.3 12.1 197
2x2.5 7/0.67 2.01 0.7 0.1 1.3 12.2 7.41 239
2x4.0 7/0.85 2.55 0.7 0.1 1.3 13.4 4.61 300
3x1.0 7/0.44 1.32 0.7 0.1 1.3 11.2 18.1 194
3x1.5 7/O.53 1.59 0.7 0.1 1.3 11.8 12.1 224
3x2.5 7/0,67 2.01 0.7 0.1 1.3 12.8 7.41 276
3x4.0 7/0.85 2.55 0.7 0.1 1.3 14.1 4.61 353
4x1.0 7/0.44 1.32 0.7 0.1 1.3 12.0 18.1 224
4x1.5 7/0.53 1.59 0.7 0.1 1.4 12.7 12.1 261
4x2.5 7/0.67 2.01 0.7 0.1 1.3 13.9 7.41 326
4x4.0 7/0.85 2.55 0.7 0.1 1.3 15.3 4.61 422

Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information

Electrical PROPERTIES

Conductor Operating Temperature : 90°C

Ambient Temperature : 30°C

Current-Carrying Capacities (Amp)

Conductor cross- sectional area Reference
method 4 (enclosed in conduit
in thermally insulating wall etc)
Reference method 3 (enclosed in conduit on
a wall or in trunking etc)
Reference method
1 (clipped direct)
Reference method 11 (on a perforated cable tray, horizontal or vertical) Reference method 12 (free air)
Horizontal flat spaced Vertical flat spaced Trefoil
  2 cables, single- phase a.c. or d.c. 3 or 4 cables,
3-phase a.c.
2 cables, single- phase a.c. or d.c 3 or 4 cables,
3-phase a.c.
2 cables, single- phase a.c. or d.c. flat and touching 3 or 4 cables,
3-phase a.c. flat and touching or trefoil
2 cables, single- phase a.c. or d.c. or flat and touching 3 or 4 cables,
3-phase a.c. flat and touching or trefoil
2 cables, single- phase a.c. or d.c.
or 3 c ables three phase
2
cables, single- phase a.c. or d.c.
or 3 cables three phase
3 cables, trefoil
3-phase a.c.
1 2 3 4 5 6 7 8 9 10 11 12
mm2 A A A A A A A A A A A
1.0 13 - - - 15 - - - - - -
1.5 18 17 22 19 25 23 - - - - -
2.5 24 23 30 26 34 31 - - - - -
4 33 30 40 35 46 41 - - - - -

Voltage Drop (Per Amp Per Meter)

Nominal
Cross
Section
Area
2 cables
d.c.
2 cables, single-phase a.c. 3 or 4 cables, 3-phase a.c.
Ref. Methods 3
and 4 (enclosed
in conduit etc,
in or on a wall)
Ref. Methods 1
and 11 (clipped
direct or on trays
touching)
Ref. Methods 3
and 4 (enclosed
in conduit etc,
in or on a wall)
Ref. Methods 1,
11 and 12 (in
trefoil)
Ref. Methods 1 and
11(Flat and touching)
1 2 3 4 5 6 7
mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
1.0 46 46 - - - -
1.5 31 31 27 27 27 27
2.5 19 19 16 16 16 16
4 33 12 10 10 10 10