| Firetox Flame Retardant Cables | |||
Firetox Flame Retardant Cables
300/500V XLPE Insulated, LSZH Sheathed, Screened Power Cables (2-4cores)
FTX200 05ROZ1-R (CU/XLPE/OSCR/LSZH 300/500V Class 2)
Application
300/500V XLPE Insulated, LSZH Sheathed, Screened Power Cables (2-4cores) are mainly used in power
stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and
high-rise buildings.
Standards
Basic design to BS 5308

Fire Performance
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2- 1*; DIN VDE 0482-265-2-1* |
|---|---|
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30- 004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2- 4 |
| Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268- 1&2*; BS 7622-1&2* |
| No Toxic gases | NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
Voltage Rating
300/500V
Cable Construction
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: Extruded cross-linked XLPE compound.
Filler, binder(if any): PP, Mylar tape
Circuit Protective Conductor: Annealed plain copper (class 2)
Overall Screen: Aluminium/polyester tape
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound
type SW2-SW4 as per BS 7655-2.6 can be offered.)
Colour Code
Insulation colour as per bs7671
| with earth conductor | without earth conductor | |
|---|---|---|
| 2Cores | - | Brown,Blue |
| 3Cores | Yellow/Green,Brown,Blue | Brown,Gray,Black |
| 4Cores | Yellow/Green,Brown,Gray,Black | Brown,Gray,Black,Blue |
| 5Cores | Yellow/Green,Brown,Gray,Black,Blue | Brown,Gray,Black,Blue,Black |
| above 5 Cores | Yellow/Green,Black Numbered | Black Numbered |
Physical And Thermal Properties
Temperature range during operation: Max.90°C for XLPE
250°C in short-circuit for 5s max.
Minimum bending radius: 6 x Overall Diameter
Construction Parameters
| Conductor | FTX200 05ROZ1-R | |||||||
|---|---|---|---|---|---|---|---|---|
| No. Of
Core X Cross Section |
No./
Nominal Diameter Of Strands |
Nominal
Overall Diameter Conductor |
Nominal
Insulation Thickness |
Cross-
Section Area Of Circuit Protective Conductor |
Nominal
Sheath Thickness |
Nominal Overall Diameter |
Max.Dc
Resistance Of Conductor @20°C |
Approx. Weight |
| Noxmm2 | No./mm | mm | mm | mm2 | mm | mm | Ω/km | kg/km |
| 2x1.0 | 7/0.44 | 1.32 | 0.6 | 1.0 | 0.9 | 8.1 | 18.1 | 79 |
| 2x1.5 | 7/0.53 | 1.59 | 0.7 | 1.5 | 0.9 | 9.1 | 12.1 | 102 |
| 2x2.5 | 7/0.67 | 2.01 | 0.8 | 2.5 | 1.0 | 10.5 | 7.41 | 146 |
| 2x4.0 | 7I0.85 | 2.55 | 0.8 | 4.0 | 1.1 | 11.8 | 4.61 | 205 |
| 3x1.0 | 7I0.44 | 1.32 | 0.6 | 1.0 | 0.9 | 8.6 | 18.1 | 98 |
| 3x1.5 | 7I0.53 | 1.59 | 0.7 | 1.5 | 0.9 | 9.6 | 12.1 | 129 |
| 3x2.5 | 7I0.67 | 2.01 | 0.8 | 2.5 | 1.0 | 11.1 | 7.41 | 185 |
| 3x4.0 | 7I0.85 | 2.55 | 0.8 | 4.0 | 1.1 | 12.5 | 4.61 | 262 |
| 4x1.0 | 7I0.44 | 132 | 0.6 | 1.0 | 1.0 | 9.5 | 18.1 | 123 |
| 4x1.5 | 7I0.53 | 1.59 | 0.7 | 1.5 | 1.0 | 10.6 | 12.1 | 162 |
| 4x2.5 | 7I0.67 | 2.01 | 0.8 | 2.5 | 1.1 | 12.3 | 7.41 | 233 |
| 4x4.0 | 7I0.85 | 2.55 | 0.8 | 4.0 | 1.2 | 13.9 | 4.61 | 329 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information
Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
| Conductor cross- sectional area | Reference method 4 (enclosed in conduit in thermally insulating wall etc) |
Reference method 3 (enclosed in conduit on a wall or in trunking etc) |
Reference method 1 (clipped direct) |
Reference method 11 (on a perforated cable tray, horizontal or vertical) | Reference method 12 (free air) | ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Horizontal flat spaced | Vertical flat spaced | Trefoil | |||||||||
| 2 cables, single- phase a.c. or d.c. | 3 or 4 cables, 3-phase a.c. |
2 cables, single- phase a.c. or d.c | 3 or 4 cables, 3-phase a.c. |
2 cables, single- phase a.c. or d.c. flat and touching | 3 or 4 cables, 3-phase a.c. flat and touching or trefoil |
2 cables, single- phase a.c. or d.c. or flat and touching | 3 or 4 cables, 3-phase a.c. flat and touching or trefoil |
2 cables, single- phase a.c. or d.c. or 3 c ables three phase |
2 cables, single- phase a.c. or d.c. or 3 cables three phase |
3 cables, trefoil 3-phase a.c. |
|
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
| mm2 | A | A | A | A | A | A | A | A | A | A | A |
| 1.5 | 18 | 17 | 22 | 19 | 25 | 23 | - | - | - | - | - |
| 2.5 | 24 | 23 | 30 | 26 | 34 | 31 | - | - | - | - | - |
| 4 | 33 | 30 | 40 | 35 | 46 | 41 | - | - | - | - | - |
| Nominal Cross Section Area |
2 cables d.c. |
2 cables, single-phase a.c. | 3 or 4 cables, 3-phase a.c. | |||
|---|---|---|---|---|---|---|
| Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) |
Ref. Methods 1 and 11 (clipped direct or on trays touching) |
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) |
Ref. Methods 1, 11 and 12 (in trefoil) |
Ref. Methods 1 and 11(Flat and touching) |
||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 |
| mm2 | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m |
| 1.5 | 31 | 31 | 27 | 27 | 27 | 27 |
| 2.5 | 19 | 19 | 16 | 16 | 16 | 16 |
| 4 | 33 | 12 | 10 | 10 | 10 | 10 |