Fire Resisting Cable


Fire Resisting Cables


Fire Resistant Coaxial Cables

Fire resistant RG6 A/U Coaxial cables

RG6 A/U FR

Application

The cables are designed for CCTV, security, smoke detection and evacuation monitoring applications, where

continued functionality is required during a fire situation. Due to the zero halogen low smoke construction,

this cable is ideal for use in public, commercial and industrial environments.

Standards

Basic design to MIL-C-17 

Fire resistant RG6 A/U Coaxial cables

Fire Performance

Circuit Integrity

IEC 60331-23; BS 6387 CWZ; DIN VDE 0472-814(FE180);

CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3);

NF C32-070-2.3(CR1)

System circuit integrity DIN 4102-12, E30 depending on lay system

Flame Retardance (Single Vertical

Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C

30-004 (cat. F1); NF C32-070-2.1(C2);

CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation

(Vertically-mounted bundled wires

& cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-

3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-

4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.

Cable Construction

Conductors: Bare copper copper wire, solid according to IEC(EN) 60228 class 1.

Insulation: Foamed PE wrapped with fire resistant silicone rubber compound type EI2 as per BS 7655-1.1 or

fluoropolymer(FEP) compound.

Binder: Glass tape

Overall Screen: AL foil(100%)+AL braid (70%)

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound

type SW2-SW4 as per BS 7655-2.6 can be offered.)

Physical And Thermal Properties

Temperature range during operation (fixed state): -30°C - +70°C

Temperature range during installation (mobile state): -5ºC - +60ºC

Minimum bending radius: 8 x Overall Diameter

Electrical Properties

Impedance:75±5Ω

Capacitance:54 nF/km

Velocity ratio(%):82

Insulation resistance :>5000 Mohm.Km

Shield coverage :AL foil(100%)+AL 70%

DC resistance

Inner conductor:23.1 Ω/km

Outer conductor:31 Ω/km

Attenuation

Frequency(MHz) Attenuation (dB/100 m) Attenuation (dB/100ft)
50 5.0 1.5
100 6.4 1.96
200 9.2 2.8
500 14.5 4.4
600 15.9 4.9
800 17.7 5.4
1000 21.9 6.7
1350 24.9 7.6
1750 29.0 8.8
2050 33.1 10.1
2400 36.4 11.1

Return Loss

Frequency(MHz) Return Loss (dB)
30-300 >28dB
300-600 >24dB
600-900 >22dB

Construction Parameters

Cable Code Conductor Diameter Nominal Insulation Diameter Nominal Screen No.x Diameter Nominal Overall Diameter Approx. Weight
mm mm No. x mm mm kg/km
RG6 A/U FR 1.02 4.57 ± 0.20 96 x 0.12 7.00 ± 0.20 81.6