  indoor tight buffer fiber optic cable  
Indoor Used Tight Buffered Fiber
Optical Cable
outdoor multi loose tube fiber optic cable
Outdoor Used Multi Loose Tube
Fiber Optical Cable
 
  Bus Cables  
Profibus DP Profibus PA Profibus SK Foundation Field Bus

Bus Cables

Profibus L2 Direct Burial

Bus Cables

Application:

This system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell and field area. For the information exchange between different automation systems as well as for communication with the connected decentralized field units, serial field bus systems are used. The above mentioned type is suitable for underground installation and is equipped with a special PVC/PE jacket.

Construction:

Type/Area of Application

Underground Laying

Cable Construction

1x2x0.64 mm

Inner Conductor Diameter 1

Copper, bare (AWG 22/1)

Conductor Insulation

Foam-Skin-PE

Conductor Colors 1

Red, green

Stranding Element

2 conductors + 2 fillers stranded together

Shielding 1

Polyester foil over stranded bundle

Shielding 2

Polyester foil, aluminum lined

Total Shielding

Copper braid, tinned

Inner Jacket Material

PVC

Outer Jacket Material

PE

Outer Diameter

10.0 mm ± 0.2 mm

Outer Jacket Color

Black

Electrical Data:

Characteristic Impedance @3-20Hz

150 Ω ± 10 Ω

Conductor Resistance

57.1 Ohm/km max.

Insulation Resistance

1.00 GOhm x km min.

Mutual Capacitance @1KHz

30.0 nF/km nom.

Working Voltage

 Max: 250 V

Test Voltage

1.5 kV

Attenuation

9.6

kHz

2.1dB/km

38.4

kHz

3.1dB/km

3.0

MHz

18.2dB/km

20.0

MHz

47.0dB/km

Technical Data:

Weight

approximately 92.0 kg/km

Min. Bending Radius for Laying

18 x OD mm

Operating Temperature Range, min.

-40 °C

Operating Temperature Range, max.

+70 °C