APPLICATION:

EN 50288-7 cables are used for transmission of analoge and digital signals in instrument and control systems at

chemistry and petr°Chemistry industry plants, power plants, natural gas and petroluem plants, etc... EN 50288-

7 cables are used in the environments which have no corrosive gases are emitted in the event of fire. In case of

fire,EN 50288-7 cables inhibit the propagation of the flames whereby the development of smoke is extremely

low.EN 50288-7 Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g.

public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. EN 50288-7 cables

are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet l°Cations; on

racks, trays, in conduits.

STANDARDS

Basic design to EN50288-7

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation(Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454
Sunlight Resistance UL 1581 section 1200
Oil Resistance ICEA S-73-532**

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile

strength/min.60% of elongation, *** denotes optional.

VOLTAGE RATING

300V

CABLE CONSTRUCTION

Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation: Extruded cross-linked XLPE compound, EN 50290. 2-29.

Pair:Two conductors twisted to form a pair

Lay-up: Pairs laid up in layers of optimum pitch

Separator: Polyester tape

Overall Screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2

Inner sheath: HFFR compound, EN 50290-2-27

Armour: Galvenized round steel wire, EN 10257-1

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound

type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti

rodent and anti termite properties can be offered as option.

COLOUR CODE

Insulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.

Outer Sheath: Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES

Temperature Range During Operation (Fixed State): -30°C – +70°C

Temperature Range During Installation (Mobile State): -5°C – +50°C

Minimum Bending Radius: 7.5 X Overall Diameter

Electrical PROPERTIES

Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C)  Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.)  
  ≤ 4 pairs 90 90 90 102 102
  all other pairs 75 75 75 85 85
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Inductance mH/km(Max.) 1
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500
CONSTRUCTION PARAMETERS

 

 

Caledonian Cable Code

RE-2X(St)HSWAH

 

No. of Triples x3xCross Section

 

Nominal Insulation Thick-ness

 

Nominal Inner Sheath Thick
-ness

Nominal
Overall Diameter Over Inner Sheath

 

Nominal Armour Wire Diameter

 

Nominal Outer Sheath Thick-ness

 

No.x3xmm2

mm

mm

mm

mm

mm

0.5mm2, Multi-striple

RE-2X(St)HSWAH 2T0.5

2x3x0.5

0.35

0.9

8.4

0.9

1.4

RE-2X(St)HSWAH 4T0.5

4x3x0.5

0.35

1.0

9.8

0.9

1.4

RE-2X(St)HSWAH 5T0.5

5x3x0.5

0.35

1.0

10.8

0.9

1.4

RE-2X(St)HSWAH 6T0.5

6x3x0.5

0.35

1.0

12.1

0.9

1.4

RE-2X(St)HSWAH 8T0.5

8x3x0.5

0.35

1.1

13.1

0.9

1.5

RE-2X(St)HSWAH 10T0.5

10x3x0.5

0.35

1.1

14.7

0.9

1.5

RE-2X(St)HSWAH 12T0.5

12x3x0.5

0.35

1.1

15.2

0.9

1.5

RE-2X(St)HSWAH 16T0.5

16x3x0.5

0.35

1.2

17.4

0.9

1.6

RE-2X(St)HSWAH 20T0.5

20x3x0.5

0.35

1.2

19.1

1.25

1.6

RE-2X(St)HSWAH 24T0.5

24x3x0.5

0.35

1.3

20.9

1.25

1.7

0.75mm2, Multi-striple

RE-2X(St)HSWAH 2T0.75

2x3x0.75

0.38

1.0

10.6

0.9

1.4

RE-2X(St)HSWAH 4T0.75

4x3x0.75

0.38

1.1

12.4

0.9

1.4

RE-2X(St)HSWAH 5T0.75

5x3x0.75

0.38

1.1

13.7

0.9

1.4

RE-2X(St)HSWAH 6T0.75

6x3x0.75

0.38

1.1

15.4

0.9

1.5

RE-2X(St)HSWAH 8T0.75

8x3x0.75

0.38

1.2

16.7

0.9

1.5

RE-2X(St)HSWAH 10T0.75

10x3x0.75

0.38

1.3

19.0

0.9

1.5

RE-2X(St)HSWAH 12T0.75

12x3x0.75

0.38

1.3

19.7

0.9

1.7

RE-2X(St)HSWAH 16T0.75

16x3x0.75

0.38

1.4

22.5

1.25

1.6

RE-2X(St)HSWAH 20T0.75

20x3x0.75

0.38

1.5

24.9

1.25

1.7

RE-2X(St)HSWAH 24T0.75

24x3x0.75

0.38

1.6

27.2

1.25

1.7

1.0mm2, Multi-striple

RE-2X(St)HSWAH 2T1.0

2x3x1.0

0.4

1.0

11.5

0.9

1.4

RE-2X(St)HSWAH 4T1.0

4x3x1.0

0.4

1.1

13.4

0.9

1.4

RE-2X(St)HSWAH 5T1.0

5x3x1.0

0.4

1.1

14.8

0.9

1.5

RE-2X(St)HSWAH 6T1.0

6x3x1.0

0.4

1.2

16.9

0.9

1.5

RE-2X(St)HSWAH 8T1.0

8x3x1.0

0.4

1.2

18.1

0.9

1.5

RE-2X(St)HSWAH 10T1.0

10x3x1.0

0.4

1.3

20.7

0.9

1.6

RE-2X(St)HSWAH 12T1.0

12x3x1.0

0.4

1.3

21.4

1.25

1.6

RE-2X(St)HSWAH 16T1.0

16x3x1.0

0.4

1.4

24.4

1.25

1.7

RE-2X(St)HSWAH 20T1.0

20x3x1.0

0.4

1.5

27.1

1.25

1.7

RE-2X(St)HSWAH 24T1.0

24x3x1.0

0.4

1.6

29.6

1.25

1.8

1.3mm2, Multi-striple

RE-2X(St)HSWAH 2T1.3

2x3x1.3

0.45

1.1

12.8

0.9

1.4

RE-2X(St)HSWAH 4T1.3

4x3x1.3

0.45

1.1

14.7

0.9

1.5

RE-2X(St)HSWAH 5T1.3

5x3x1.3

0.45

1.2

16.5

0.9

1.5

RE-2X(St)HSWAH 6T1.3

6x3x1.3

0.45

1.3

18.8

0.9

1.5

RE-2X(St)HSWAH 8T1.3

8x3x1.3

0.45

1.3

20.1

0.9

1.6

RE-2X(St)HSWAH 10T1.3

10x3x1.3

0.45

1.4

23.0

1.25

1.7

RE-2X(St)HSWAH 12T1.3

12x3x1.3

0.45

1.5

24.0

1.25

1.7

RE-2X(St)HSWAH 16T1.3

16x3x1.3

0.45

1.6

27.4

1.25

1.8

RE-2X(St)HSWAH 20T1.3

20x3x1.3

0.45

1.7

30.4

1.25

1.8

RE-2X(St)HSWAH 24T1.3

24x3x1.3

0.45

1.8

33.1

1.60

1.9

1.5mm2, Multi-striple

RE-2X(St)HSWAH 2T1.5

2x3x1.5

0.45

1.1

13.2

0.9

1.4

RE-2X(St)HSWAH 4T1.5

4x3x1.5

0.45

1.2

15.4

0.9

1.5

RE-2X(St)HSWAH 5T1.5

5x3x1.5

0.45

1.2

17.1

0.9

1.5

RE-2X(St)HSWAH 6T1.5

6x3x1.5

0.45

1.3

19.5

0.9

1.6

RE-2X(St)HSWAH 8T1.5

8x3x1.5

0.45

1.4

21.1

1.25

1.6

RE-2X(St)HSWAH 10T1.5

10x3x1.5

0.45

1.5

24.1

1.25

1.7

RE-2X(St)HSWAH 12T1.5

12x3x1.5

0.45

1.5

24.9

1.25

1.7

RE-2X(St)HSWAH 16T1.5

16x3x1.5

0.45

1.6

28.4

1.25

1.8

RE-2X(St)HSWAH 20T1.5

20x3x1.5

0.45

1.7

31.6

1.25

1.9

RE-2X(St)HSWAH 24T1.5

24x3x1.5

0.45

1.8

34.4

1.60

2.0

             
Note : Other conductor sizes & core configurations are available upon request.