BS 5467 Cables  
BS 5467 Armoured Power Cables EEMUA 133 Lead covered armoured Power Cables to BS 5467
BS 5467 Cables

BS 5467 Armoured Power Cables, 600/1000V

Three-core 600/1000 V cables with stranded copper conductors

Application

BS 5467 cables are used for power and control circuits, BS 5467 can offer excellent protection through the use of

a heavy galvanized steel wire armour. The GSWA makes them suitable for use inside and outside buildings or for

direct burial in the ground.

Construction

Conductor Solid Aluminum or Copper conductor, round stranded or shaped, Class 2 to BS 6460, IEC 60228.
Insulation Colour Code XLPE (Cross-Linked Polyethylene) Type GP 8 or ethylene propylene rubber (GP 6) 1 Core : Brown
  3 Cores: Brown, Black, Grey
Bedding Armour Outer Sheath extruded layer of polymeric material

Technical Information

Voltage rating 600/1000V

Temperature rating0°C to +90°C

Bending radius1.5mm² to 16mm²: 6 x overall diameter

                        25mm² and above: 8 x overall diameter

Flame retardantIEC60332 part 1, BS4066 part 1

BS 5467 Armoured Power Cables, 600/1000V

Nominal Nominal Insula- Nominal Nominal Steel Armour
strip
Nominal Approx. Overall Diameter Aprrox
Weight
Cross-sectional Area tion thickness bedding
thickness
Wire Armor dia. thickness width Sheath thickness wire armor strip armor
Extruded bedding Taped
bedding
mm² mm mm mm mm mm mm mm mm mm kg/km
3x16 0.7 0.8 1.25 0.6 2.4 1.6 20.3 20.3 19 760
3x25 0.9 1 1.6 0.6 2.4 1.7 22.5 22.1 20.1 1020
3x25* 0.9 1 1.6 0.6 2.4 1.7 24.9 24.5 22.5 1020
3x35 0.9 1 1.6 0.6 2.4 1.8 24.4 24.9 22 1200
3x35* 0.9 1 1.6 0.6 2.4 1.8 27.3 26.9 24.9 1200
3x50* 1.0 1 1.6 0.6 2.4 1.8 26.8 26.4 24.9 1380
3x70* 1.1 1 1.6 1 3.6 1.9 30.2 29.8 28.6 1750
3x95* 1.1 1.2 2.0 1 3.6 2.1 34.8 34.0 32 2420
3x120* 1.2 1.2 2.0 1.4 4.8 2.2 37.8 37.0 35.8 2820
3x150* 1.4 1.4 2.5 1.4 4.8 2.3 42.7 41.5 39.3 3660
3x185* 1.6 1.4 2.5 1.4 4.8 2.4 46.7 45.5 43.3 4350
3x240* 1.7 1.4 2.5 1.4 4.8 2.6 51.5 50.3 48.1 5220
3x300* 1.8 1.6 2.5 1.8 6.4 2.7 56.2 54.6 53.2 6200