BS 5467 Cables  
BS 5467 Armoured Power Cables EEMUA 133 Lead covered armoured Power Cables to BS 5467
BS 5467 Cables

BS 5467 Armoured Power Cables, 1900/3300V

Single-core 1900/3300 V cables with solid aluminum conductor

Application

BS 5467 Cables are used for power and control circuits, they can offer excellent protection through the use of a

heavy galvanized steel wire armour. The GSWA makes them suitable for use inside and outside buildings or for

direct burial in the ground.

Construction

Conductor Solid Aluminum or Copper conductor, round stranded or shaped, Class 2 to BS 6460, IEC 60228.
Insulation Colour Code XLPE (Cross-Linked Polyethylene) Type GP 8 or ethylene propylene rubber (GP 6) 1 Core : Brown
  3 Cores: Brown, Black, Grey
Bedding Armour Outer Sheath extruded layer of polymeric material

Technical Information

Voltage rating 1900/3300V

Temperature rating 0°C to +90°C

Bending radius 1.5mm² to 16mm²: 6 x overall diameter

                          25mm² and above: 8 x overall diameter

Flame retardant IEC60332 part 1, BS4066 part 1

BS 5467 Armoured Power Cables, 1900/3300V

Nominal Cross-sectional Area Nominal Insulation thickness Nominal beddingthickness Nominal Alum Wire Armor dia. Nominal Sheath thickness Approx.Overall Diameter AprroxWeight
mm² mm mm mm mm mm kg/km
1x50 2 0.8 1.25 1.6 19.4 600
1x70 2 0.8 1.25 1.6 20.9 710
1x95 2 0.8 1.25 1.6 22.5 810
1x120 2 1 1.6 1.7 25.2 1065
1x150 2 1 1.6 1.7 26.5 1210
1x185 2 1 1.6 1.8 28.3 1390
1x240 2 1 1.6 1.8 30.5 1630
1x300 2 1 1.6 1.9 32.8 1900